Page 5

M-UM038-01 RP 460 Reference and Test

DMT

Example 2: Singlemode Fiber, Point-to-Point, 2 Jumpers

Fiber Type

Singlemode

Connectors Used

LC

Test Jumper Setup

Double

OPM Used

RP 460

OLS Used

DLS 355

Fiber-Under-Test

The fiber-under-test is singlemode with LC 

connectors on each end. This method allows testing 

of connectors inside bulkheads. One or both ends of 

this fiber-under-test may be inside bulkheads. The 

fiber-under-test may be up to 250 kilometers long. 

In this example, the fiber-under-test is 400 meters 

long.

Test Jumpers

The test jumpers are both one-meter singlemode 

fiber. One has one SC and one LC connector, and 

the other has two LC connectors.

400m Fiber

Connectors Inside Bulkheads

1m Jumpers

Power Meter

The RP 460 power meter is set to the 

1550nm wavelength. The 1310nm 

wavelength may also be used. Always 

match the wavelength on the RP 460 

to the wavelength on the DLS 355. The 

adapter on the RP 460 is the AC 029 LC 

adapter.

Light Source

The DLS 355 laser source is set to the 

1550nm wavelength. The 1310nm 

wavelength may also be used. The 

adapter is the default AC 022B SC adapter.

Содержание ODM RP 460

Страница 1: ...RP 460 How to Set a Reference and Perform an Insertion Loss Test...

Страница 2: ...LS This document outlines the specific steps which must be taken with ODM s RP 460 optical power meter to perform insertion loss testing on a variety of fiber types and setups Example 1 Singlemode Fib...

Страница 3: ...t jumper is a one meter singlemode fiber with SC and LC connectors The SC connector will be plugged into the DLS 355 laser source and the LC connector will be used to interface with the fiber under te...

Страница 4: ...fter 5 seconds release the dB dBm button The RP 460 screen will display 0 00dB with some minor variation DO NOT switch the RP 460 back to the dBm mode Between 5 00 and 7 00dBm Hold for 5 seconds Refer...

Страница 5: ...ilometers long In this example the fiber under test is 400 meters long Test Jumpers The test jumpers are both one meter singlemode fiber One has one SC and one LC connector and the other has two LC co...

Страница 6: ...n for 5 seconds After 5 seconds release the dB dBm button The RP 460 screen will display 0 00dB with some minor variation DO NOT switch the RP 460 back to the dBm mode Between 5 00 and 7 00dBm Hold fo...

Страница 7: ...ting One end has an SC connector and an LC connector and the other end has two LC connectors clipped together This method also uses a singlemode loopback adapter It should be blue and have a duplex bu...

Страница 8: ...for 5 seconds After 5 seconds release the dB dBm button The RP 460 screen will display 0 00dB with some minor variation DO NOT switch the RP 460 back to the dBm mode Between 5 00 and 7 00dBm Hold for...

Страница 9: ...ultimode fiber with SC and LC connectors The SC connector will be plugged into the DLS 350 LED source and the LC connector will be used to interface with the fiber under test Power Meter The RP 460 po...

Страница 10: ...ds After 5 seconds release the dB dBm button The RP 460 screen will display 0 00dB with some minor variation DO NOT switch the RP 460 back to the dBm mode Between 22 and 25dBm Hold for 5 seconds Refer...

Страница 11: ...esting One end has an SC connector and an LC connector and the other end has two LC connectors clipped together This method also uses a multimode loopback adapter It should be black and have a duplex...

Страница 12: ...Test Jumper and the Fiber Under Test should be cleaned to appropriate standards Use an inspection scope to verify fiber cleanliness Plug the clipped LC end of the Test Jumper into one end of the Fiber...

Отзывы: