Charging with continuous current U-I

 

 
For special purposes where a stable voltage and current are required, the AP-3000 also 
provides this function. The charging current is continuous, it can be chosen from ‘Battery 
Type’ menu heading by selecting ‘UI’. In the sub-menu choose ‘UoIo Menu’, which 
appears automatically. Now you can set the desired voltage and current, and confirm with 
"OK". The system automatically enters the "Status menu" and on the upper right hand 
corner of the screen we see the inscription ‘UI’. 
There are technical constraints of the AP-3000, for example, it is not possible to set a

 

 

 

   

 

 

 

     

 

   

   

voltage of 62V and current 50A at the same time. (This example relates to the AP-3000

   

 

 

 

   

 

 

 

 

 

   

 

 

48V battery charger). 
 
 

Selected voltage 

 Uo

 

Max selected current  

Io

 

>66.0V

 

10.5A 

64.0V

 

12.2A 

62.0V

 

15.8A 

60.0V

 

29.8A 

59.2V

 

40.2A 

<59.2V 

50.0A 

 

 
 
 

** Mains Voltage Too Low ** 

 

In the case of the mains voltage being too low, (considered to be all voltages below 210V

 

 

   

 

 

 

 

 

 

   

   

 

 

 

AC), the charging current is automatically reduced by up to 35% of the nominal value. This

 

 

 

   

 

       

   

 

 

 

 

occurs down to a voltage of 90V AC. The device can therefore also be used in

 

 

   

 

 

 

 

 

 

 

 

 

 

   

environments where mains voltage fluctuates significantly. Current from the mains will

 

 

 

 

 

 

 

 

 

 

 

never exceed 16A. The charger is automatically protected against damage, as too is the

 

 

 

 

   

 

 

 

 

 

   

 

mains supply. The the mains fuse is 16A. Charge current is reduced in steps, as shown in

 

 

 

 

 

   

 

 

   

   

   

   

the table below. Mains voltage is displayed in the status menu, bottom left. If the charger is

 

 

 

 

   

   

 

 

 

 

   

 

   

in standby and is not charging, the display shows the mains voltage with a considerable

 

 

   

 

 

 

 

 

 

 

 

   

 

error. During charging, the measurement error of mains voltage is minimum. 

 

Uac[V]  210  200  190  180  170  160  150  140  130  120  110  100  90 
Ibat[%]  95 

90 

85 

80 

75 

70 

65 

60 

55 

50 

45 

40 

35 

 
 
 
 
 
 
 

 
 
 
 

RIPCHARGE UK, 3 CUTTS CLOSE, BRINKWORTH, CHIPPENHAM, WILTSHIRE, ENGLAND, UK. 
+44 (0) 1666 510626 e-mail:[email protected] 

Содержание AP-3000 Pb

Страница 1: ...Instructions For use Rapid Impulse Phase Battery Charger Models AP 3000 Pb 12V 135A 24V 100A 36V 75A 48V 50A...

Страница 2: ...charging of starter battery Connector for attachment of outside led indicator Automatic detection of battery attachment yellow led Precise indication of overcharging green LED Working temperature rang...

Страница 3: ...minutes Rapid Impulse Phase charging technology works as a mediator between battery chemistry and signals that instruct every charge Each battery is treated individually Charging Instructions How to o...

Страница 4: ...menu BattType select the type of battery In menu Disp Contrast set the best screen visibility In menu Burst force the charger to charge when the battery is fully discharged Battery select menu Turn t...

Страница 5: ...When the battery charger is disconnected from the battery charge value CAP and the charging time TIME remain in memory When beginning a new charge cycle these values will be reset Contrast MENU By usi...

Страница 6: ...rent limit MENU By using the selection button and pressing to confirm you can set limit of the charging current in the range of 20 to 100 based on the rated charging current Battery Size MENU By using...

Страница 7: ...UoIo Menu By using the selection button and confirm by pressing select the desired voltage Uo 48 0V 68 0V and Io 1 8A 50A Finally confirm with OK to leave the menu Calibrate Heading calibration of the...

Страница 8: ...0A Mains Voltage Too Low In the case of the mains voltage being too low considered to be all voltages below 210V AC the charging current is automatically reduced by up to 35 of the nominal value This...

Страница 9: ...supply network example fuse limited the charging current in this case can be reduced to 20 of nominal Charging current is reduced in steps of 10 In the case of setting the charging current to 20 of t...

Страница 10: ...ks bulk charge 65 yellow on constantly absorption I charge Abso1 65 75 green blinks absorption II charge Abso2 75 90 green 2x fast blink Equalization charge Equ 90 95 green on constantly float charge...

Страница 11: ...eling traction batteries Operational Problems Error Cause Solution The charger is connected to the mains power switch is ON LED is not flashing the screen does not work there is no mains voltage 230Va...

Страница 12: ...urrent 4 5mA 240Vac klase I Protection Short circuit no voltage on output if battery is not connect Start charge at 6V 12V 18V 24V Reverse polarity Save active protect acoustic buzzer active Error on...

Отзывы: