8
Rinnai Direct Vent Service Manual
Analog
Indicator
Light
Digital
LED
Name Definition Corrective
Action
LO-HI
PF --
:--
Power Failure Electric power has
been lost while the
appliance was running
Check that the power cord is firmly inserted into
the electrical outlet.
Check the 3 amp fuse.
Check whether the fuse or breaker has blown at
the switch board.
60
11
Missed Ignition Flame rod current
does not reach 1.0
microamp within a
certain time after the
solenoid opens.
Check that the flame rod is firmly positioned.
Check the flame rod lead.
Check the flame rod for carbon build up.
Check that the correct gas is being used.
Check the supply pressure at the meter and at
the appliance.
Check that there are no leaks in the gas supply
line or appliance.
Check for air in the gas supply.
LO
12
Flame Failure Flame rod current
remains below 1.0
microamp for 3
seconds during initial
combustion
Check that the correct gas is being used.
Check the supply pressure at the meter and at
the appliance.
Check that there are no leaks in the gas supply
line or appliance.
Check for air in the gas supply.
68 14
Overheat
Safety
Device
High limit temperature
thermistor or thermal
fuse has activated
Check that the correct gas is being used.
Check the supply pressure at the meter and at
the appliance.
Check that the flue terminal is not blocked.
Check that the air filter is not blocked.
Check that the warm air flow is not blocked.
(There should be a clearance of 40 inches in front
of the appliance.)
HI 16 Over
Temperature
Cut Off
Room temperature is
above 104ºF for
longer than 10
minutes
Check that the correct gas is being used.
Check the supply pressure at the meter and at
the appliance.
Check that the flue terminal is not blocked.
Check that the air filter is not blocked.
Check that the warm air flow is not blocked.
(There should be a clearance of 40 inches in front
of the appliance.)
72 76
31
Room
Temperature
Thermistor
Disconnection
Room temperature
thermistor circuit is
open
Check the circuit. (troubleshooting)
76 80
32
Room
temperature
thermistor short
circuit
Room temperature
thermistor wire is
trapped or touching
bare metal.
Check the circuit. (troubleshooting)
Fault Isolation Codes
Содержание RHFE-431WTA
Страница 14: ...14 Rinnai Direct Vent Service Manual RHFE 431FA Series RHFE 556FA FTRA Wire Diagram ...
Страница 15: ...Rinnai Direct Vent Service Manual 15 RHFE 556FAIII Wire Diagram ...
Страница 16: ...16 Rinnai Direct Vent Service Manual RHFE 556FTRAIII Wire Diagram ...
Страница 24: ...24 Rinnai Direct Vent Service Manual RHFE 431WTA Wire Diagram ...
Страница 25: ...Rinnai Direct Vent Service Manual 25 RHFE 556WTA Wire Diagram ...
Страница 31: ...Rinnai Direct Vent Service Manual 31 RHFE 551FA Wire Diagram ...
Страница 34: ...34 Rinnai Direct Vent Service Manual RHFE 1001FA Wire Diagram ...
Страница 37: ...Rinnai Direct Vent Service Manual 37 RHFE 1001FA VA Wire Diagram Wire Diagram Block Diagram ...
Страница 42: ...42 Rinnai Direct Vent Service Manual RHFE 201FA Wire Diagram ...
Страница 43: ...Rinnai Direct Vent Service Manual 43 RHFE 201FA Block Diagram ...
Страница 46: ...46 Rinnai Direct Vent Service Manual RHFE 263FA RHFE 263FAII Wire Diagram ...
Страница 47: ...Rinnai Direct Vent Service Manual 47 RHFE 263FA RHFE 263FAII Block Diagram ...
Страница 50: ...50 Rinnai Direct Vent Service Manual RHFE 1004FA Wire Diagram ...
Страница 67: ...Rinnai Direct Vent Service Manual 67 Notes ...