HE+ Series Modulating Supplemental Manual

 

13.  FIELD  CONVERSION OF FUEL GAS: HE+ SERIES MODULATING BURNERS 

 

 

Tube Heater Burners are factory produced and supplied to operate on natural gas.

 

A field conversion kit is available from Rinnai and must be used to convert from natural gas to pro-
pane gas, or vice versa. Each kit contains the required parts and specific instructions to make the 
gas conversion.  Refer to the table below for kit part numbers.

 

NOTE: All Kits include a Gas Orifice*, and Valve Conversion Kit with Pressure Regulator 

Spring and Cap, and instructions to convert the gas valve and install the kit.

 

* Gas Orifice in the Field Conversion Kit:

 

◼ 

USA: 0 to 2,000 ft 

 

◼ 

Refer to 

High Altitude

” 

section for altitudes higher than listed above

 

Gas Conversion Kits 

-

 Order by Part Number

 

 

Input Rate   

(BTUH) 

 

Conversion Kit

 

NG to PROPANE

 

80,000

 

903000052

 

115,000

 

903000053

 

155,000

 

903000054

 

205,000

 

903000055

 

260,000

 

903000056

 

TABLE 

6

 

GAS CONVERSON KITS 

 

Содержание RHEPM11530N

Страница 1: ......

Страница 2: ...h any open flame Do not attempt to light this or any other appliance Don t touch any electrical switch or telephone Immediately call your gas supplier from a neighbor s phone Follow any and all instru...

Страница 3: ...ANUAL INCLUDED FOR THIS SERIES HEATER GENERAL MANUAL TABLE OF CONTENTS TOPIC PAGE IMPORTANT INFORMATION READ FIRST APPLICATION 4 HEATER EXPANSION 5 31 GAS CONNECTION 5 31 VENTING 5 26 START UP SMOKE 5...

Страница 4: ...resi dential dwelling If installation of this equipment is in question consult with the local authority having jurisdiction Fire Marshall labor department insurance underwriter or other Revisions to c...

Страница 5: ...97 RHEPM15540N RHEPM15550N NG PROPANE 155 000 100 000 40 40 11 197 50 50 7 239 RHEPM20550N RHEPM20560N NG PROPANE 205 000 125 000 50 50 7 239 60 60 3 282 RHEPM25060N RHEPM25070N NG PROPANE 250 000 160...

Страница 6: ...L center air intake to end 50 49 11 3 4 599 3 4 1523 cm 60 59 7 3 4 715 3 4 1818 cm 70 69 3 3 4 831 3 4 2113 cm 80 78 11 3 4 947 3 4 2407 cm FIGURE 2 HANGER SPACING LENGTH AIR INTAKE TO VENT END POSI...

Страница 7: ...nized Steel Hot Rolled Steel 155 000 50 RHEPP3AHMX RHEPS2HHS1S2 Aluminized Steel Hot Rolled Steel 205 000 50 RHEPP3AH RHEPS2HHS1S2 Aluminized Steel Hot Rolled Steel 205 000 60 RHEPP3AH RHEPS3HHS1S2 Al...

Страница 8: ...RHEPP2AHM RHEPP3AHM RHEPP3AHMX RHEPP4AHMX RHEPP4AHMX 30 ft PRIMARY RHEPP3AHMX RHEPS2HHS1S2 20 ft SECONDARY RHEPP3AH RHEPS2HHS1S2 20 ft SECONDARY RHEPS3HHS1S2 30 ft SECONDARY RHEPP3AH RHEPP4SS RHEPS2HH...

Страница 9: ...9 HE Series Modulating Supplemental Manual This Page Intentionally Left Blank...

Страница 10: ...CTION REQUIRED REMOVE DISCARD TURBULATOR SECTION NG or LP 80 000 x 20 4 x 2 25 x 36 1 IN 1st TUBE 3 IN 2nd TUBE No action required NG or LP 115 000 x 30 3 x 2 25 x 36 1 IN 2nd TUBE 2 IN 3rd TUBE No ac...

Страница 11: ...rade Twelve inches from flue vent terminal of any heater with input up to 100 000 Btu hr Three feet from flue vent terminal of any heater over 100 000 Btu hr An optional horizontal fresh air intake ho...

Страница 12: ...cated exhaust fan Exhaust must be located as high as practicable in the structure above the level of the heater s Consult your local code and ANSI Z223 1 latest edition for all venting requirements an...

Страница 13: ...m each heater is not required to be equidis tant to the vent Tee but must comply with local code requirements A common thermostat or ON OFF switch must control the two commonly vented heaters Common v...

Страница 14: ...uration of the vent must allow for heater expansion VERTICAL VENT Orientation of the vent at 90 to heater will allow for heater expansion and contraction HORIZONTAL VENT See FIG 7 Wall Thimble or flas...

Страница 15: ...d supported without any dips or sags and shall slope upward toward the vent or chimney at least 1 4 in ft 20 mm m Use a certified termination cap as supplied by the manufacturer of the vent When vent...

Страница 16: ...gases Install termination cap a minimum of 18 inches 45 cm from the outside wall to the inside edge of terminal opening to alleviate back pressure caused by turbulent wind conditions See Fig 8 This al...

Страница 17: ...ination clearance The bottom of the vent terminal and the air intake shall be located at least 12 inches 305 mm above grade A horizontal vent will not terminate Less than 3 ft 915 mm above a mechanica...

Страница 18: ...ostat control must be installed in the thermostat circuit from the terminal block TR TW A line voltage Thermostat or an ON OFF control switch installed in the 120VAC power supply will disable the post...

Страница 19: ...19 HE Series Modulating Supplemental Manual 8A HE SERIES WIRING DIAGRAM 24V OR 120 VOLT THERMOSTAT OPERATION ONE HEATER PER THERMOSTAT P N 905000020 Red Red Black...

Страница 20: ...20 HE Series Modulating Supplemental Manual 8B HE SERIES MULTIPLE TUBE HEATERS PER COMMON THERMOSTAT P N 905000020 Red 905000035 905000035 Red Black...

Страница 21: ...r one hour the control will automatically reset and attempt to ignite the burner again three trials At any time less than the 1 hour auto reset recovery from lockout requires a manual reset by either...

Страница 22: ...rature of 160 F All connec tions should be made with UL approved 105 C rated 18 gauge stranded 054 thick insulated wire Refer to wire diagram page 35 when con necting the Series 35 61 to other compone...

Страница 23: ...booklet format pages folded in half then use these bars IF this manual is printed 8 5 x 11 full page format use these bars OR AD SERVICE CHECKS Flame current passes through the flame from the sensor...

Страница 24: ...eck LED for steady on D 24VDC Power Unit is bad E Modulating Controller bad 3 Pressure switch input okay but no Trial for Ignition after purge delay A Mis wired check PSW terminal voltage 24Vac 10 B F...

Страница 25: ...SWITCH REPLACE DEFECTIVE SWITCH VISIBLY CHECK IF IGNITER IS SHORTING OUT CHECK GROUND WIRING REMOVE AND INSPECT IGNITER AND LEAD CHECK BOOT OF THE IGNITION CABLE FOR SIGNS OF MELTING OR OVERHEATING IF...

Страница 26: ...EVEN THOUGH OPERATION IS NOR MAL AT THE TIME OF CHECKOUT CHECK FOR EXCESSIVE HEAT AT SENSOR INSU LATOR AS TEMPERATURES ABOVE 1000 F 538 C CAUSES SHORT TO GROUND CHECK FLAME SIGNAL IN SERIES WITH THE...

Страница 27: ...NDITIONS ARE COMPATIBLE WITH THIS HEATER AND TO THIS EQUIPMENT HAS BEEN FACTORY FIRED AND TESTED PRIOR TO SHIPMENT HOW EVER THIS APPLIANCE IS NOT PLUG PLAY IT REQUIRES COMMISSIONING AND FIELD ADJUSTME...

Страница 28: ...AGE READING AT THE IGNITION MODULE VOLTS WHAT IS THE FLAME SIGNAL STRENGTH IN uA FROM SENSOR uA microamps IS HEATER CONTROLLED BY A THERMOSTAT YES NO IS THE THERMOSTAT STRATEGICALY LOCATED YES NO WHAT...

Страница 29: ...ns to make the gas conversion Refer to the table below for kit part numbers NOTE All Kits include a Gas Orifice and Valve Conversion Kit with Pressure Regulator Spring and Cap and instructions to conv...

Страница 30: ...l utility regarding de rating and the following specifically for country of installation 14 A ORIFICE CONVERSION TABLE 7 RINNAI RECOMMENDED ORIFICES ALTITUDE CONVERSION MODEL INPUT RATE MBH FOR USE AT...

Страница 31: ...w intensity heater Q Letter Size Propane 906000128 Gas orifice low intensity heater 19 Number Size 250 NG 906000100 Gas orifice low intensity heater R Letter Size Propane 906000104 Gas orifice low int...

Страница 32: ...RAIN PIPING ALL Customer Supplied Pipe Nipples Union and Elbow 18 GAS VALVE MODULATING ALL NG Propane 906000129 Modulating Gas Valve 19 MODULATING CONTROLLER 80 NG Propane 905000037 Modulating Tube He...

Страница 33: ...EEL RIVET 225 to 250 1st to 2nd 2nd to 3rd tube connections 906000121 Tube Connection Kit Coupler Rivet 225 to 250 1st to 2nd 2nd to 3rd tube 42 COUPLER Aluminized Steel ALL 906000117 4 swaged tube co...

Страница 34: ...34 HE Series Modulating Supplemental Manual NOTES...

Страница 35: ...35 HE Series Modulating Supplemental Manual NOTES...

Страница 36: ......

Отзывы: