HE+ Series Modulating Supplemental Manual

 

9. FENWAL DSI: SEQUENCE OF OPERATION / FLAME RECOVERY / SAFETY LOCKOUT

 

Power Up / Stand By 

 

Upon applying 24 volts power to 24VAC, the control will reset, perform a self check routine, initiate full 
time flame sensing, and enter the thermostat scan state. 

 

Heat Mode 

 

When a call for heat is received from the thermostat supplying 24 volts to TH, the control checks the 

pressure switch for normally open contacts. The combustion blower is then energized and once the 

pressure switch contacts close, a 30 second purge delay begins. Following the purge period the gas 

valve is energized and spark commences for the 15 second trial for ignition. 

 

When flame is detected during the trial for ignition, spark is shutoff immediately and the gas valve com-

bustion blower remains energized. The thermostat, pressure switch, and main burner flame are con-

stantly monitored to assure the system continues to operate properly. 

 

• 

For the first two minutes, the heater operates on Low

-

fire 

 

• 

After 2 minutes, it runs on Hi

-

Fire for next 5 minutes, irrespective of Modulating signal from the ther-

mostat

 

• 

After total of 7 minutes, the heater responds to the modulating signal( 2

-

10V) from the thermostat

 

When the thermostat is satisfied and the demand for heat ends, the main valve is de

-

energized immed-

iately, the control senses the loss of flame signal and initiates a 30 second post

-

purge period before de

-

energizing the combustion blower. 

 

Failure to Ignite 

-

 Lockout 

 (

THREE TRIAL MODEL

 

This three

-

try control will attempt two additional ignition trials with a 30 second inter

-

purge between tri-

als, before going into 

soft

’ 

lockout. The valve relay will be de

-

energized immediately, and the combus-

tion blower will be turned off following the 30 second post purge period. 

 

If the thermostat continues to call for heat after one hour the control will automatically reset and attempt 

to ignite the burner again (three trials). 

 

At any time less than the 1 hour auto

-

reset, recovery from lockout requires a manual reset by either re-

setting the thermostat or removing 24 volts for a period of 5 seconds. 

 

Flame Failure 

-

 Re

-

cycle

 

If the established flame signal is lost while the burner is operating, the control will go to recycle mode. 

The HV spark will be energized for a trial ignition period in an attempt to relight the burner. If the burner 

does not light the control will de

-

energize the gas valve. Two more attempts will be made to relight the 

burner. If the  burner does not relight the control will go into 

soft

’ 

lockout as noted above in 

Failure to 

Light

”. 

If flame is re

-

established, normal operation resumes. 

 

 

 

Combustion Airflow Problems 

-

Lockout 

 

Combustion air flow is continually monitored during an ignition sequence by the air flow switch (PSW). 

If during the initial call for heat the pressure contacts are in the closed position for 30 seconds without 

an output to the Combustion Blower, an air flow fault will be declared and the control will remain in this 

mode with the combustion blower off. 

 

If the air flow switch remains open for more than 30 seconds after the combustion blower output (L1 & 

IND) is energized, an air flow fault will be declared and the control will stay in this mode with the com-

bustion blower on, waiting for the air flow switch to close. 

 

When proper air flow is detected from the air flow switch input (PSW) the control begins the pre

-

purge period followed with a 15 second ignition sequence. 

 

If the air flow signal is lost while the burner is firing, the control will immediately de

-

energize the gas 

valve and the combustion blower will remain on. If the call for heat remains, the control will wait for 

proper air flow to return. If proper air flow is not detected after 30 seconds an air flow fault signal will be 

declared. If proper air flow is detected at any time, a normal sequence will begin with the pre

-

purge pe-

riod. 

 

Содержание RHEPM11530N

Страница 1: ......

Страница 2: ...h any open flame Do not attempt to light this or any other appliance Don t touch any electrical switch or telephone Immediately call your gas supplier from a neighbor s phone Follow any and all instru...

Страница 3: ...ANUAL INCLUDED FOR THIS SERIES HEATER GENERAL MANUAL TABLE OF CONTENTS TOPIC PAGE IMPORTANT INFORMATION READ FIRST APPLICATION 4 HEATER EXPANSION 5 31 GAS CONNECTION 5 31 VENTING 5 26 START UP SMOKE 5...

Страница 4: ...resi dential dwelling If installation of this equipment is in question consult with the local authority having jurisdiction Fire Marshall labor department insurance underwriter or other Revisions to c...

Страница 5: ...97 RHEPM15540N RHEPM15550N NG PROPANE 155 000 100 000 40 40 11 197 50 50 7 239 RHEPM20550N RHEPM20560N NG PROPANE 205 000 125 000 50 50 7 239 60 60 3 282 RHEPM25060N RHEPM25070N NG PROPANE 250 000 160...

Страница 6: ...L center air intake to end 50 49 11 3 4 599 3 4 1523 cm 60 59 7 3 4 715 3 4 1818 cm 70 69 3 3 4 831 3 4 2113 cm 80 78 11 3 4 947 3 4 2407 cm FIGURE 2 HANGER SPACING LENGTH AIR INTAKE TO VENT END POSI...

Страница 7: ...nized Steel Hot Rolled Steel 155 000 50 RHEPP3AHMX RHEPS2HHS1S2 Aluminized Steel Hot Rolled Steel 205 000 50 RHEPP3AH RHEPS2HHS1S2 Aluminized Steel Hot Rolled Steel 205 000 60 RHEPP3AH RHEPS3HHS1S2 Al...

Страница 8: ...RHEPP2AHM RHEPP3AHM RHEPP3AHMX RHEPP4AHMX RHEPP4AHMX 30 ft PRIMARY RHEPP3AHMX RHEPS2HHS1S2 20 ft SECONDARY RHEPP3AH RHEPS2HHS1S2 20 ft SECONDARY RHEPS3HHS1S2 30 ft SECONDARY RHEPP3AH RHEPP4SS RHEPS2HH...

Страница 9: ...9 HE Series Modulating Supplemental Manual This Page Intentionally Left Blank...

Страница 10: ...CTION REQUIRED REMOVE DISCARD TURBULATOR SECTION NG or LP 80 000 x 20 4 x 2 25 x 36 1 IN 1st TUBE 3 IN 2nd TUBE No action required NG or LP 115 000 x 30 3 x 2 25 x 36 1 IN 2nd TUBE 2 IN 3rd TUBE No ac...

Страница 11: ...rade Twelve inches from flue vent terminal of any heater with input up to 100 000 Btu hr Three feet from flue vent terminal of any heater over 100 000 Btu hr An optional horizontal fresh air intake ho...

Страница 12: ...cated exhaust fan Exhaust must be located as high as practicable in the structure above the level of the heater s Consult your local code and ANSI Z223 1 latest edition for all venting requirements an...

Страница 13: ...m each heater is not required to be equidis tant to the vent Tee but must comply with local code requirements A common thermostat or ON OFF switch must control the two commonly vented heaters Common v...

Страница 14: ...uration of the vent must allow for heater expansion VERTICAL VENT Orientation of the vent at 90 to heater will allow for heater expansion and contraction HORIZONTAL VENT See FIG 7 Wall Thimble or flas...

Страница 15: ...d supported without any dips or sags and shall slope upward toward the vent or chimney at least 1 4 in ft 20 mm m Use a certified termination cap as supplied by the manufacturer of the vent When vent...

Страница 16: ...gases Install termination cap a minimum of 18 inches 45 cm from the outside wall to the inside edge of terminal opening to alleviate back pressure caused by turbulent wind conditions See Fig 8 This al...

Страница 17: ...ination clearance The bottom of the vent terminal and the air intake shall be located at least 12 inches 305 mm above grade A horizontal vent will not terminate Less than 3 ft 915 mm above a mechanica...

Страница 18: ...ostat control must be installed in the thermostat circuit from the terminal block TR TW A line voltage Thermostat or an ON OFF control switch installed in the 120VAC power supply will disable the post...

Страница 19: ...19 HE Series Modulating Supplemental Manual 8A HE SERIES WIRING DIAGRAM 24V OR 120 VOLT THERMOSTAT OPERATION ONE HEATER PER THERMOSTAT P N 905000020 Red Red Black...

Страница 20: ...20 HE Series Modulating Supplemental Manual 8B HE SERIES MULTIPLE TUBE HEATERS PER COMMON THERMOSTAT P N 905000020 Red 905000035 905000035 Red Black...

Страница 21: ...r one hour the control will automatically reset and attempt to ignite the burner again three trials At any time less than the 1 hour auto reset recovery from lockout requires a manual reset by either...

Страница 22: ...rature of 160 F All connec tions should be made with UL approved 105 C rated 18 gauge stranded 054 thick insulated wire Refer to wire diagram page 35 when con necting the Series 35 61 to other compone...

Страница 23: ...booklet format pages folded in half then use these bars IF this manual is printed 8 5 x 11 full page format use these bars OR AD SERVICE CHECKS Flame current passes through the flame from the sensor...

Страница 24: ...eck LED for steady on D 24VDC Power Unit is bad E Modulating Controller bad 3 Pressure switch input okay but no Trial for Ignition after purge delay A Mis wired check PSW terminal voltage 24Vac 10 B F...

Страница 25: ...SWITCH REPLACE DEFECTIVE SWITCH VISIBLY CHECK IF IGNITER IS SHORTING OUT CHECK GROUND WIRING REMOVE AND INSPECT IGNITER AND LEAD CHECK BOOT OF THE IGNITION CABLE FOR SIGNS OF MELTING OR OVERHEATING IF...

Страница 26: ...EVEN THOUGH OPERATION IS NOR MAL AT THE TIME OF CHECKOUT CHECK FOR EXCESSIVE HEAT AT SENSOR INSU LATOR AS TEMPERATURES ABOVE 1000 F 538 C CAUSES SHORT TO GROUND CHECK FLAME SIGNAL IN SERIES WITH THE...

Страница 27: ...NDITIONS ARE COMPATIBLE WITH THIS HEATER AND TO THIS EQUIPMENT HAS BEEN FACTORY FIRED AND TESTED PRIOR TO SHIPMENT HOW EVER THIS APPLIANCE IS NOT PLUG PLAY IT REQUIRES COMMISSIONING AND FIELD ADJUSTME...

Страница 28: ...AGE READING AT THE IGNITION MODULE VOLTS WHAT IS THE FLAME SIGNAL STRENGTH IN uA FROM SENSOR uA microamps IS HEATER CONTROLLED BY A THERMOSTAT YES NO IS THE THERMOSTAT STRATEGICALY LOCATED YES NO WHAT...

Страница 29: ...ns to make the gas conversion Refer to the table below for kit part numbers NOTE All Kits include a Gas Orifice and Valve Conversion Kit with Pressure Regulator Spring and Cap and instructions to conv...

Страница 30: ...l utility regarding de rating and the following specifically for country of installation 14 A ORIFICE CONVERSION TABLE 7 RINNAI RECOMMENDED ORIFICES ALTITUDE CONVERSION MODEL INPUT RATE MBH FOR USE AT...

Страница 31: ...w intensity heater Q Letter Size Propane 906000128 Gas orifice low intensity heater 19 Number Size 250 NG 906000100 Gas orifice low intensity heater R Letter Size Propane 906000104 Gas orifice low int...

Страница 32: ...RAIN PIPING ALL Customer Supplied Pipe Nipples Union and Elbow 18 GAS VALVE MODULATING ALL NG Propane 906000129 Modulating Gas Valve 19 MODULATING CONTROLLER 80 NG Propane 905000037 Modulating Tube He...

Страница 33: ...EEL RIVET 225 to 250 1st to 2nd 2nd to 3rd tube connections 906000121 Tube Connection Kit Coupler Rivet 225 to 250 1st to 2nd 2nd to 3rd tube 42 COUPLER Aluminized Steel ALL 906000117 4 swaged tube co...

Страница 34: ...34 HE Series Modulating Supplemental Manual NOTES...

Страница 35: ...35 HE Series Modulating Supplemental Manual NOTES...

Страница 36: ......

Отзывы: