Installation Manual

COMMISSIONING

TESTING

1.

Before final connection of the water heater purge gas, hot water and cold water supply lines.
Swarf in either the gas or water supplies may cause damage.

2.

Turn on gas and cold water supplies. 

3.

Test for water leaks and gas escapes near the unit. 

4.

Isolate gas supply. Remove test point screw located on the gas inlet connection and attach
pressure gauge.

5.

Turn the power 'on' at the power point socket and turn on gas. 

6.

Ensure controllers are 'ON', select the maximum delivery temperature and open ALL available
hot water taps including the shower. If remote controllers are not fitted, simply open all available
hot water taps. (CAUTION: Ensure building occupants do not have access to hot water outlets
during this procedure.) 

7.

Operate ALL other gas appliances at their maximum gas rate, in accordance with manufacturers
instructions.

8.

With all gas appliances in operation at maximum gas rate, the pressure should read between
1.13 - 3.0 kPa on Natural Gas. On LPG the pressure should be 2.75 - 3.0 kPa. If the pressure is
lower, the gas supply is inadequate and the appliance will not operate to specification. It is the
Installers responsibility to check the gas meter, service regulator and pipe work for correct
operation/sizing and rectify as required. Note that the gas regulator on the appliance is
electronically controlled and factory pre-set. Under normal circumstances it DOES NOT need
adjustment during installation.

9.

Close hot water taps including the shower.

10. Inspect and clean the strainer located on the cold water inlet connection. This procedure may

need to be repeated to ensure the strainer remains clear, especially on new installations.

11. If water controllers are fitted, it is necessary to test their operation through the complete range of

functions (refer to the Operation sections of this manual). 

12. Confirm the hot water delivery temperature(s) using a thermometer. If controllers are fitted,

ensure temperatures exceeding 50°C cannot be selected on bathroom or ensuite controllers.
Refer to the section ‘Delivery Temperature’ below for more details.

13. After testing is completed, explain to the householder the functions and operation of the water

heater and water controllers (if fitted). Ensure the “PRODUCT RECORDS” on page 42 of this
manual is filled in and that the booklet is handed to the customer. Reminding the customer to
complete the Warranty Card and forward to Rinnai.

DELIVERY TEMPERATURE

"50°C Compliant" appliances are 'factory set' to deliver a maximum temperature not exceeding 50°C.
However, they have an incremental adjustment mechanism that allows the installer to increase the
appliance delivery temperature incrementally from the 'Factory Set’ value to temperatures exceeding
50°C. This is intended to enable compensation for temperature losses in the pipe-work between the
water heater and any outlets and achieve the required temperature at the outlet. Instructions for
incremental temperature adjustment are located in the instruction pocket inside the appliance front
cover. 

For all other models 

Rinnai continuous flow water heaters are factory pre-set to various maximum delivery temperatures
depending on model and their intended application. For the majority of applications, the factory pre-
set temperature is appropriate. In the unlikely event it is not this setting can be increased or decreased
by the installer. Instructions for changing the maximum delivery temperature are located in the
instruction pocket inside the appliance front cover. 

Содержание infinity 26 touch REU-VRM2626WD

Страница 1: ......

Страница 2: ...This page is intentionally blank...

Страница 3: ...WATER CONTROLLER 15 ADJUSTING TEMPERATURE 15 HOW TO USE TWO OR MORE UNIVERSAL WATER CONTROLLERS 16 TRANSFERRING PRIORITY 16 ADJUSTING TEMPERATURE 16 DELUXE BATHROOM WATER CONTROLLERS 17 ABOUT THE DELU...

Страница 4: ...ontact the Plumbing Industry Commission on 1800 015 129 Heated water can be dangerous especially for young children and the infirm Water temperatures above 50 C can cause severe burns instantly and ma...

Страница 5: ...ain when the temperature falls below the selected temperature The burner lights automatically when the hot water tap is opened and goes out when the tap is closed IGNITION IS ELECTRONIC so there is no...

Страница 6: ...at the outlet There is no need to turn the water controller s off after use However if you prefer to turn the water controller s off selected temperatures to a maximum of 50 C will be stored in the s...

Страница 7: ...may discharged from the flue outlet This condition is normal for high efficiency appliances and does not indicate a fault Keep flammable materials spray cans fuel containers pool chemicals trees shrub...

Страница 8: ...disabled elderly and the infirm Hot water at 65 C a very common hot water temperature in Australia can severely burn a child in less than half a second At 50 C it takes five minutes ALWAYS Test the te...

Страница 9: ...tly the hot water unit will deliver the selected temperature even when the water flow is varied or more than one tap is in use Each remote controller can be individually programmed however the water h...

Страница 10: ...ter controllers allow temperature selection only Deluxe water controllers allow temperature selection have a clock function and on the Deluxe Bathroom water controller BC 100V a shower saver bath fill...

Страница 11: ...owered to a minimum of 37 C For safety it cannot then be raised above 43 C until all hot water taps are closed If the water heater is turned Off whilst hot water taps are open it can not be turned bac...

Страница 12: ...ssign the wireless transceiver if this is the case See UN ASSIGNING AND RESETTING WIRELESS WATER CONTROLLERS on page 36 and INSTALLING WIRELESS WATER CONTROLLERS on page 34 USING CHILD LOCK FUNCTION T...

Страница 13: ...er body Then turn the battery compartment cover a full turn clockwise to obtain the correct seal 5 Return the controller to the wall mounting bracket Use only 2 x 1 5V AAA alkaline batteries DO NOT mi...

Страница 14: ...tor and the In Use indicator will illuminate signifying that the preheat system has been activated 4 Wait approximately two minutes before opening an outlet This will allow the water in the pipework t...

Страница 15: ...may be lowered However they cannot then be raised above 43 C In addition transfer of priority between controllers is not possible These are safety features The beep sound can be muted by pressing the...

Страница 16: ...Use indicator will illuminate on the water controller Once the hot water is running if the set temperature is either too hot or cold press the Hot water temp or buttons until the desired temperature i...

Страница 17: ...E AT BUT TON Indicates the selected hot water temperature WATER TEM PER ATURE INDIC ATOR Indicates that the Shower Saver Bath Fill function has been selected and that a shower is running or the bath i...

Страница 18: ...normal mode press the Clock button once if no buttons are pressed for a period of approximately 60 seconds the controller will return to normal mode The time is always displayed regardless of whether...

Страница 19: ...ended period To select the volume of water to be used in the shower bath use the Water Volume or buttons The selected volume is displayed in large digits to the right and will remain as the default Wa...

Страница 20: ...Follow the voice prompt instructions When Shower Saver Bath Fill Operations Finishes Once the Shower Saver Bath Fill operation finishes the following events will occur 1 The flow from the shower bath...

Страница 21: ...controller is fitted press the Transfer button to transfer priority to the desired controller SETTING THE SOUND OPTIONS Voice prompts only available when Deluxe Bathroom water controller s are instal...

Страница 22: ...the water controller is turned ON or OFF The clock may need resetting if power to the water heater unit is disrupted due to a power failure or if the power is switched off over a prolonged period ADJU...

Страница 23: ...This will allow the water in the pipework to be warmed Other Controller Functions Controller functions such as temperature control and transfer of priority between multiple controllers is not affecte...

Страница 24: ...stance from transceiver or an obstruction Move wireless water controller or transceiver or remove the obstruction Noticeable reduction in water flow Inlet water filter needs to be cleaned Service call...

Страница 25: ...Rinnai Australia 25 Installation Manual NOTES...

Страница 26: ...Rinnai Australia 26 Operation Manual This page is intentionally blank...

Страница 27: ...ING WIRELESS WATER CONTROLLERS 34 WIRELESS WATER CONTROLLER INSTALLATION 35 INSTALLING MULTIPLE WIRELESS WATER CONTROLLERS 35 TROUBLE SHOOTING WIRELESS WATER CONTROLLERS CHANNEL ASSIGNMENT 36 UN ASSIG...

Страница 28: ...w and return system or the Rinnai Smartstart system can be used which minimise the waiting time for hot water delivery Alternatively multiple appliances can be strategically placed to serve outlets wi...

Страница 29: ...xceeding 50 C or your local regulations require installation with a Temperature Limiting Device then install the appliance in accordance with Diagram 2 page 29 Ensure that suitable fixing screws or bo...

Страница 30: ...fitted Master and Sub controllers and temperatures Only one wireless or wired controller can be designated the Master Controller MC This controller is normally used in the kitchen and usually has a ma...

Страница 31: ...nside the building Take the signal strength into consideration when determining the best location for both the transceiver and the wireless water controllers Other manufacturers water controllers are...

Страница 32: ...to 50 MJ hr input 150 Other appliances up to 50 MJ hr input 500 Appliances over 50 MJ h input and up to 150 MJ h input 1000 Appliances over 150 MJ h input 1500 1 Where dimensions c j or k cannot be ac...

Страница 33: ...ove does not apply when multiple Rinnai external water heaters of the same model are installed on the same vertical face with flue terminals at the same height Under these conditions appliances can ab...

Страница 34: ...1 Ensure the power to the water heater is switched on 2 Set the transceiver s maximum water temperature to 55 C by pressing the Max Temp button until 55 is displayed Refer to Master and Sub controlle...

Страница 35: ...and hold the On Off button until screen C is displayed This takes approximately 2 seconds 6 From screen C press the On Off button once to start the tuning process which will take approximately 5 secon...

Страница 36: ...ocedures to enable these options When installing combinations of both wired and wireless controllers all wired water controllers MUST BE connected before the wireless water controllers are assigned to...

Страница 37: ...ransceiver or when an object is obstructing the radio signal Wireless water controllers should be positioned such that the signal strength indicator displays at least 2 bars next to the antenna symbol...

Страница 38: ...water controller Feed any excess cable lengths into the wall cavity to avoid the pinching of cables between the wall and the controller As supplied the water heater is not pre wired for the installati...

Страница 39: ...ure for the fourth controller you may ignore Question 2 Fig 5 Fig 6 Is the water heater marked to state it delivers water not exceeding 50 C IF YES No further action required IF NO You will need to pr...

Страница 40: ...fixings as this may cause damage Once secured replace the face plate Fig 2 Fig 3 Fig 4 Fig 5 1 Determine the most suitable position for the water controller see notes page 38 2 Mark and drill 3 holes...

Страница 41: ...s clear especially on new installations 11 If water controllers are fitted it is necessary to test their operation through the complete range of functions refer to the Operation sections of this manua...

Страница 42: ...t can also assist the installer to identify potential installation errors that may prevent the appliance from operating correctly Recess Box These allow the appliance to be recessed into the cavity of...

Страница 43: ...Rinnai Australia 43 Installation Manual NOTES...

Страница 44: ...OIM INFINITY TOUCH 13 031 Issue 1 05 02 14 44 CONTACT INFORMATION...

Отзывы: