Infinity REU-V3232W /HD250E REU-V3232WC
- 36 -
Issue 1 - 8/09/03 ©Rinnai
c.)
Disconnect relay connector (J1) and ( J3)
and measure resistance between Yellow and
Yellow on Heat Exchanger Heater side.
Normal:
825
Ω
If normal, proceed to Frost Sensing Switch
18.
Faulty:
Replace Anti-frost Heater A (assy).
[Measure when temperature is 4+/- 3
o
C.]
Note: If you cannot get the temperature
low enough, cool the low-temperature
sensing switch with ice etc.
18. Frost Sensing Switch
a.)
Disconnect relay connector (J
2
) and measure
resistance between Blue and Blue.
Normal:
< 1
Ω
If normal, check wiring (AC240V circuit).
Faulty:
Replace Frost Sensing Switch.