ddTT11SSCC sets the minimum temperature difference
between the heat pump leaving water
temperature (T1) and the heat pump leaving
water set temperature (T1S) at which the heat
pump provides chilled water to the space cooling
terminals.
When T1
–
T1S
≥
dT1SC the heat pump provides
chilled water to the space cooling terminals and
when T1
≤
T1S the heat pump does not provide
chilled water to the space cooling terminals.
FFRREEDDDDO
O
T4: outside temperature
T1: Heat pump leaving water temperature
T1S: Heat pump leaving water set temperature
CCO
OO
OLL
ddTTSSCC sets the temperature difference between
the actual room temperature (Ta) and set room
temperature (TS) above which the heat pump
provides chilled water to the space cooling
terminals.
When Ta
–
TS
≥
dTSC the heat pump provides
chilled water to the space cooling terminals and
when Ta
≤
TS the heat pump does not provide
chilled water to the space cooling terminals.
Refer to figure
dTSC is only applicable if YES is selected for
ROOM TEMP in the TEMP. TYPE SETTING menu.
Refer to Part
“
TEMP. TYPE SETTING Menu
CCO
OO
OLL
tt__IINNTTEERRVVAALL__CC sets the cooling mode compressor
re-start delay. When the compressor stops
running, it will not re-start until at least
t_INTERVAL_C minutes have elapsed.
TT11SSeettCC11 sets the temperature 1 of automatic
setting curve for cooling mode.
TT11SSeettCC22 sets the temperature 2 of automatic
setting curve for cooling mode.
TT44CC11 sets the outside temperature 1 of
automatic setting curve for cooling mode.
TT44CC22 sets the outside temperature 2 of
automatic setting curve for cooling mode.
ZZO
ONNEE11 CC--EEM
MIISSSSIIO
ONNII sets the emission type of
zone1 for cooling mode.
Select type:
RAD = radiators (do not use)
CVC = fancoil
CRP = radiant panels
ZZO
ONNEE22 CC--EEM
MIISSSSIIO
ONNII sets the emission type of
zone2 for cooling mode.
Select type:
RAD = radiators (do not use)
CVC = fancoil
CRP = radiant panels
In COOL MODE SETTING the following parameters
should be set.
CCO
OO
OLL M
MO
ODDEE enables or disables cooling mode.
For installations with space cooling terminals,
select YES to enable cooling mode.
For installations without space cooling terminals,
select NON to disable cooling mode.
tt__TT44__FFRREESSHH__CC sets the refresh time of cooling
model climate temperature curve.
TT44CCM
MAAXX sets the outside temperature above
which the heat pump will not operate in cooling
mode. The maximum value that T4CMAX can take
is 46°C, which is the cooling mode upper outside
temperature operating limit of the heat pump.
TT44CCM
MIINN sets the outside temperature below which
the heat pump will not operate in cooling mode.
The lowest value that T4CMIN can take is -5°C,
which is the cooling mode lower outside
temperature operating limit of the heat pump.
Refer to figure
M
Meennuu HHEEAATTIINNGG M
MO
ODDEE SSEETTTTIINNGG
M
MEENNU
U >> FFO
ORR SSEERRVVIICCEEM
MAANN >> HHEEAATT M
MO
ODDEE SSEETTTTIINNGG
In HEAT MODE SETTING the following parameters
should be set.
HEAT MODE enables or disables heating mode.
tt__TT44__FFRREESSHH__HH sets the refresh time of heating
model climate temperature curve .
TT44HHM
MAAXX sets the outside temperature above
which the heat pump will not operate in heating
mode.
The highest value that T4HMAX can take is 35°C,
which is the heating mode upper outside
temperature operating limit of the heat pump.
Refer to figure
T4: outside temperature
TT44HHM
MIINN sets the outside temperature below which
the heat pump will not operate in heating mode.
The lowest value that T4HMIN can take is -25°C,
which is the heating mode lower outside
temperature operating limit of the heat pump.
ddTT11SSHH sets the temperature difference between
the heat pump leaving water temperature (T1)
and the heat pump leaving water set temperature
(T1S) above which the heat pump provides
heated water to the space heating terminals
ddTTSSHH sets the temperature difference between
the actual room temperature (Ta) and set room
temperature (TS) above which the heat pump
provides heated water to the space heating
terminals.
When TS
–
Ta
≥
dTSH the heat pump provides
heated water to the space heating terminals and
when Ta
≥
TS the heat pump does not provide
heated water to the space heating terminals.
Refer to figure
dTSH is only relevant if YES is selected for
OUTSIDE TEMP in the TEMP. TYPE SETTING menu.
Refer to Part
“
TEMP. TYPE SETTING Menu
”.
HHEEAATT
NotE:
Only when ROOM TEMP is enabled will this function be available
tt__IINNTTEERRVVAALL__HH sets the heating mode compressor
re-start delay. When the compressor stops
running, it will not re-start until at least
t_INTERVAL_H minutes have elapsed.
TT11SSeettHH11 sets the temperature 1 of automatic
setting curve for heating mode.
TT11SSeettHH22 sets the temperature 2 of automatic
setting curve for heating mode.
TT44HH11 sets the outside temperature 1 of
automatic setting curve for heating mode.
TT44HH22 sets the outside temperature 2 of
automatic setting curve for heating mode.
HHEEAATT
T4HMIN
T4HMAX
DELAY_PUMP
StaRt - up