REU-2532W Series
44
Rinnai
Unable to adjust hot water temperature
1) Is the water temperature thermistor operating normally ?
a.
# Disconnect the connector B
5,
and measure the
resistance between the white wires, see below
for resistance readings.
Thermistor resistance valves:
59 ºF = 11.4 ~ 14 K
Ω
86 ºF = 6.4 ~ 7.8 K
Ω
113 ºF = 3.6 ~ 4.5 K
Ω
140 ºF = 2.2 ~ 2.7 K
Ω
221 ºF = 0.6 ~ 0.8
Ω
Normal:
Proceed to check item 2 below.
Faulty:
Replace the water temperature
thermistor.
2) Is the change over solenoid (SV1) normal ?
a.
# Disconnect the changeover solenoid (SV1)
connector, and measure resistance at the
solenoid terminals.
Normal:
1.7 ~ 2.1 K
Ω
If normal, proceed to b.
Faulty:
Replace the changeover solenoid (SV1).
b.
Measure the voltage at the changeover solenoid
(SV1) yellow ~ black wires.
Normal:
80 ~ 100 VDC
If normal, proceed to check item 3, on next
page.
Faulty:
Replace the PCB unit.
Содержание Continuum REU2532-W Series
Страница 8: ...REU 2532W Series 8 Rinnai 3 Dimensions...
Страница 9: ...REU 2532W Series 9 Rinnai 4 Installation Piping recommendation...
Страница 16: ...REU 2532W Series 16 Rinnai 9 Cut way Diagram REU 2532 FFU Series...
Страница 17: ...REU 2532W Series 17 Rinnai 10 Schematic Diagram REU 2532W Series...
Страница 26: ...REU 2532W Series 26 Rinnai 15 Time Charts External Unit...
Страница 27: ...REU 2532W Series 27 Rinnai...
Страница 35: ...REU 2532W Series 35 Rinnai 20 REU 2532W Series Wiring...
Страница 36: ...REU 2532W Series 36 Rinnai 21 Block Diagram...
Страница 60: ...REU 2532W Series 60 Rinnai 26 EXPLODED VIEW CABINET...
Страница 61: ...REU 2532W Series 61 Rinnai EXPLODED VIEW INTERNALS...
Страница 62: ...REU 2532W Series 62 Rinnai EXPLODED VIEW INTERNALS...
Страница 63: ...REU 2532W Series 63 Rinnai EXPLODED VIEW ELECTRICAL...