RM5000EX Operations Manual September 2018
BATTERY CHARGE MONITOR
When the RM5000EX is equipped with battery backup the battery voltage is monitored. If the
input voltage is higher then 25 Volt then the battery is being charged and the light LDP1_CH is ON.
If AC power is lost or the battery charger fails then the battery voltage will fall below the 25 Volt and
LDP1_CH will turn OFF. At the same time Power Fail Alarm may be sent to the DAD104 (if
programmed) and the system is running on battery power. This alarm can only be cleared by restoring
the battery voltage to 25 Volt or higher.
PROGRAMMING
The following commands are used for this feature.
SCN
Set Call Number
SCID
Set Caller ID
SNA
Set Network Address
LCN
List Call Number
Example: Subscribers 10 has a DAD104 with network address 09 (hex). Power Fail Alarms from the
EX500 are to be sent to this DAD. First we assign call number 00 to the EX500 at Line Equipment
Number 4F(hex).
>SCN
cr
Call Number <10-99/*> : 00
cr
Line Equipment Number <$00..$3F> : 4F
cr
>SCID 00 EX500
cr
>SNA
cr
Call Number <10-99/*> : 00
cr
Node Type (1=Annunciator 2=Printer 3=Video) <1..3> : 1
cr
Network Address <$00..$FF> : 09
cr
>LCN
cr
Call Number <10-99/*> : 00
cr
Line Call In Priority
Equ. Number Caller ID Type QUE Alarm Call Annunciator Printer Video
==== ======== ========= ==== ==== ==== ==== =========== ======= ====
$4F 00 EX500 ICM RING 1 5 09 … ...
>
PAGING
Allows for one way paging from one station to other stations in the exchange and will override
calls in progress (they will reconnect when the Page is completed).There are 15 paging groups in the
Page28