9 Troubleshooting

 

9 Troubleshooting 

 

- 50 - 

 

<Abnormalities of Readings> 

 

Symptoms Causes 

Actions 

The reading rises 
(drops) and it remains 
so. 

Drifting of sensor 
output 

Perform the zero adjustment. 

Presence of 
interference gas 

Interference gas test including solvents are identified, 
and be treated properly. 

Slow leak 

A very small amount of the gas to be detected may be 
leaking (slow leak). Because ignoring it may cause 
dangers, take a remedial measure, i.e., taking actions 
the same as those for the gas alarm. 

Environmental 
changes 

Perform the zero adjustment (AIR adjustment). 

A gas alarm is triggered 
despite of no gas leak 
and no other 
abnormalities at the 
detection point. 

Presence of 
interference gas 

Interference gas test including solvents are identified, 
and be treated properly. 

Disturbance by 
noise 

Turn off and restart the detector.   
If such a symptom is observed frequently, take 
appropriate measures to eliminate the noise. 

Sudden change in 
the environment 

When the environment (temperature, etc.) changes 
suddenly, the detector cannot adjust to it and is affected 
by it. 
In some cases, the detector triggers an indication alarm. 
Because the detector cannot be used under sudden and 
frequent environmental changes, any preventive actions 
should be taken to eliminate them by the user. 

Slow response 

Clogged dust filter 

Replace the dust filter. 

Bended, clogged, or 
leaked suction tube 
or exhaust tube 

Fix the defective parts. 

Condensation is 
formed inside the 
suction tube. 

Fix the defective parts. 

Deteriorated sensor 
sensitivity 

Replace the sensor with a new one. 

Sensitivity calibration 
impossible 

Improper calibration 
gas concentration 

Use the proper calibration gas. 

Deteriorated sensor 
sensitivity 

Replace the sensor with a new one. 

 
 
 

<Abnormalities of installation environment> 

Symptom/Display FAULT 

Causes 

Actions 

Out of operating 

temperature 

range 

E-27

 

― 

The environmental 
temperature is out of 
operating temperature 
range

 

Operating temperature range 
-20 to +60

 

If environmental temperature is out of operating 
temperature range, countermeasure for 
adjusting environmental temperature is needed 
to be considered. 

 
 
 

Содержание SD-1DRI

Страница 1: ...PT2E 2981 Smart transmitter Gas Detector Head SD 1DRI TYPE MED EX Operating Manual PT2E 196...

Страница 2: ...as detector in a place where the temperature changes drastically about 10 15 or more 3 The alarm must be set within a range where the performance of the detector can be ensured In facilities compliant...

Страница 3: ...How to wire 18 4 7 How to tube 22 How to Operate 23 5 1 Preparation for start up 23 5 2 Basic operating procedures 23 5 3 How to start the detector 24 5 4 Modes 25 5 5 Maintenance Mode User 26 5 6 Ho...

Страница 4: ...ses or other reasons leak with the built in gas sensor The concentrations of detected gases are displayed on the seven segment LED The detector outputs gas concentration in 4 20 mA An external pump et...

Страница 5: ......

Страница 6: ......

Страница 7: ......

Страница 8: ......

Страница 9: ......

Страница 10: ......

Страница 11: ......

Страница 12: ......

Страница 13: ......

Страница 14: ......

Страница 15: ...prevented by installing a lightning arrester before the field devices and central processing equipment For information on how to use a lightning arrester please contact the manufacturer Grounding In...

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ......

Страница 29: ......

Страница 30: ...ull scale is detected the sensor may be contaminated In such a case in order to ensure the reliability of the detector carry out zero calibration and span calibration properly 6 2 Fault alarm activati...

Страница 31: ......

Страница 32: ......

Страница 33: ...m the zero adjustment after ensuring that no other gases exist around it Alarm Test Inspect the alarm circuit by using the alarm test function Gas Adjustment Perform the sensitivity calibration by usi...

Страница 34: ...ks the activation of the external alarm such as a buzzer Gas Adjustment Performs the sensitivity calibration by using the calibration gas Gas Alarm Check Checks the gas alarm by using the calibration...

Страница 35: ......

Страница 36: ......

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ......

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ......

Страница 45: ...adjustment has not been completed Check if the correct concentration span adjustment gas has been provided and check the gas adjustment tool for a gas leak If there are mistakes perform the span adjus...

Страница 46: ......

Страница 47: ...3 8 years 1 After replacements having need of operation check by professional service engineers To maintain the safety operation of the detector please use our maintenance service Request RIKEN KEIKI...

Страница 48: ......

Страница 49: ...detector If such a symptom is observed frequently take appropriate measures to eliminate the noise Sensor abnormalities E 1 The sensor is not connected or improperly connected Check if the sensor cab...

Страница 50: ...ent When the environment temperature etc changes suddenly the detector cannot adjust to it and is affected by it In some cases the detector triggers an indication alarm Because the detector cannot be...

Страница 51: ...alog transmission in common with power supply power supply signal common or Two wire analog transmission digital transmission HART communication Transmission specification 4 20mADC linear load resista...

Страница 52: ......

Страница 53: ......

Страница 54: ......

Страница 55: ...ower explosive limit LEL of the combustible gas to be detected is set to 100 vol A unit used to express the percentage of a specific substance or gas in a volume of solution Calibration Adjusts the re...

Страница 56: ...Revision Date issued 0 First edition 11 10 2020 1 P9 Safety information Declaration of Conformity P53 Added CH4 0 100vol to the list of gases to be detected MED specification P55 Added vol to the defi...

Страница 57: ......

Отзывы: