6 Operations and Functions
6-2. Fault alarm activation
- 30 -
<Response to Gas Alarm>
A gas concentration value exceeds the alarm setpoint
When a gas alarm is triggered, take actions in accordance with your management rules of gas alarm.
Normally, take the following actions.
Check the reading of the detector.
NOTE
If a gas leak is momentary, the reading may already have dropped when checking it. In addition, when the
alarm is triggered by noise or other incidental conditions other than a gas, the reading may have already
dropped.
Based on your management rules of gas alarm, no one can be allowed to access the monitored zone to
ensure safety.
If the gas concentration display continues to be displayed, close the main valve of the gas, and then check
that the gas concentration reading dropped.
Equipped with a protective gear to avoid dangers caused by possibly remaining gases, before accessing
the gas leak point, and then check that gases remain by using a portable gas detector.
Determine that the point is free from dangers, and take actions to fix the gas leak.
NOTE
When high concentration gas exceeding full scale is detected, the sensor may be contaminated.
In such a case, in order to ensure the reliability of the detector, carry out zero calibration and span
calibration properly.
6-2. Fault alarm activation
A fault alarm is triggered when the detector detects abnormalities. After a fault alarm is triggered, the fault
lamp (yellow) lights up and an error message is displayed on the LCD. Determine the causes and take
appropriate actions.
After the detector is successfully returned from the fault, it restarts with the process normally performed
right after it is turned on (initial clear).
If the detector has problems and is repeatedly malfunctioning, contact our overseas sales department or
local representatives immediately.
<Display Operation>
Fault Detail Display
Display a message indicating the fault detail.
Fault Lamp (FAULT: Yellow)
This lights up when a failure occurs.
NOTE
For information on malfunctions (error messages), see "9. Troubleshooting".
6-3. Warning activation
When the environmental temperature exceeds the operating temperature of the detector, gas
concentration and warning number [E-27] are shown alternately. Since this case is not failure, still the
detector works. It outputs 4-20mA depending on gas concentration and does not light up failure lamp.
Operating temperature
:
-20 - +60
℃
(non-rapidly-vary)
Содержание SD-1DRI
Страница 1: ...PT2E 2981 Smart transmitter Gas Detector Head SD 1DRI TYPE MED EX Operating Manual PT2E 196...
Страница 5: ......
Страница 6: ......
Страница 7: ......
Страница 8: ......
Страница 9: ......
Страница 10: ......
Страница 11: ......
Страница 12: ......
Страница 13: ......
Страница 14: ......
Страница 16: ......
Страница 17: ......
Страница 18: ......
Страница 19: ......
Страница 20: ......
Страница 21: ......
Страница 22: ......
Страница 23: ......
Страница 24: ......
Страница 25: ......
Страница 26: ......
Страница 27: ......
Страница 28: ......
Страница 29: ......
Страница 31: ......
Страница 32: ......
Страница 35: ......
Страница 36: ......
Страница 37: ......
Страница 38: ......
Страница 39: ......
Страница 40: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ......
Страница 46: ......
Страница 48: ......
Страница 52: ......
Страница 53: ......
Страница 54: ......
Страница 57: ......