9 Troubleshooting

 

9 Troubleshooting 

 

 

- 49 - 

 

 
 
 
 
 

Troubleshooting 

 
 
 
 
The troubleshooting does not explain the causes of all the malfunctions which occur on the detector. This 
simply helps to find the causes of malfunctions which frequently occur. If the detector shows a symptom 
which is not explained in this manual, or still has malfunctions even though remedial actions are taken, 
please contact our overseas sales department or local representatives. 
 

<Abnormalities on Unit> 

Symptom/Display FAULT 

Causes 

Actions 

The power 

cannot be turned 

on. 

The wiring is not correct. 

Connect the wiring properly. 

The terminal plate is 
removed. 

Connect the terminal plate properly. 

Abnormalities/momentary 
blackout of power supply 
system 

Provide the rated voltage. 
Check the UPS, power supply line filter and 
insulation transformer, and then take additional 
measures. 

Cable abnormalities 
 (open circuit/not 
connected/short circuit) 

Check the wiring of detector and related 
devices around it. 

Abnormal 

operations 

Disturbances by sudden 
surge noise, etc. 

Turn off and restart the detector. 
If such a symptom is observed frequently, take 
appropriate measures to eliminate the noise. 

Sensor 

abnormalities 

E-1 

 

The sensor is not 
connected or improperly 
connected. 

Check if the sensor cable is securely fastened 
to the terminal plate. 

Zero drift caused by 
environmental changes or 
aging deterioration is out 
of the range of the 
threshold 

Perform the zero adjustment. If the symptom 
persists after the zero adjustment, replace the 
sensor with a new one. 

Faults of the sensor 

Replace the sensor with a new one. 

System 

abnormalities 

E-9 

 

The rated voltage is not 
supplied to the detector. 

Check the power supply, and supply the rated 
voltage. It occurs when the voltage of the power 
supply falls below 17.0 V. 

Abnormalities of ROM, 
RAM or EEPROM inside 
of the detector 

Please contact our overseas sales department 
or local representatives. 

Output signal (4-20mA) 
does not work correctly. 

Check if the cable for external output is correctly 
connected. (Deterioration of the cable, 
connection of the host system, etc). 
If the output is not necessary, connect a 
resistance to the terminal as mentioned in P16. 
If it is correctly connected, contact our overseas 
sales department or local agents because a 
failure inside this detector might be occurred. 

Содержание SD-1DRI

Страница 1: ...PT2E 2981 Smart transmitter Gas Detector Head SD 1DRI TYPE MED EX Operating Manual PT2E 196...

Страница 2: ...as detector in a place where the temperature changes drastically about 10 15 or more 3 The alarm must be set within a range where the performance of the detector can be ensured In facilities compliant...

Страница 3: ...How to wire 18 4 7 How to tube 22 How to Operate 23 5 1 Preparation for start up 23 5 2 Basic operating procedures 23 5 3 How to start the detector 24 5 4 Modes 25 5 5 Maintenance Mode User 26 5 6 Ho...

Страница 4: ...ses or other reasons leak with the built in gas sensor The concentrations of detected gases are displayed on the seven segment LED The detector outputs gas concentration in 4 20 mA An external pump et...

Страница 5: ......

Страница 6: ......

Страница 7: ......

Страница 8: ......

Страница 9: ......

Страница 10: ......

Страница 11: ......

Страница 12: ......

Страница 13: ......

Страница 14: ......

Страница 15: ...prevented by installing a lightning arrester before the field devices and central processing equipment For information on how to use a lightning arrester please contact the manufacturer Grounding In...

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ......

Страница 29: ......

Страница 30: ...ull scale is detected the sensor may be contaminated In such a case in order to ensure the reliability of the detector carry out zero calibration and span calibration properly 6 2 Fault alarm activati...

Страница 31: ......

Страница 32: ......

Страница 33: ...m the zero adjustment after ensuring that no other gases exist around it Alarm Test Inspect the alarm circuit by using the alarm test function Gas Adjustment Perform the sensitivity calibration by usi...

Страница 34: ...ks the activation of the external alarm such as a buzzer Gas Adjustment Performs the sensitivity calibration by using the calibration gas Gas Alarm Check Checks the gas alarm by using the calibration...

Страница 35: ......

Страница 36: ......

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ......

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ......

Страница 45: ...adjustment has not been completed Check if the correct concentration span adjustment gas has been provided and check the gas adjustment tool for a gas leak If there are mistakes perform the span adjus...

Страница 46: ......

Страница 47: ...3 8 years 1 After replacements having need of operation check by professional service engineers To maintain the safety operation of the detector please use our maintenance service Request RIKEN KEIKI...

Страница 48: ......

Страница 49: ...detector If such a symptom is observed frequently take appropriate measures to eliminate the noise Sensor abnormalities E 1 The sensor is not connected or improperly connected Check if the sensor cab...

Страница 50: ...ent When the environment temperature etc changes suddenly the detector cannot adjust to it and is affected by it In some cases the detector triggers an indication alarm Because the detector cannot be...

Страница 51: ...alog transmission in common with power supply power supply signal common or Two wire analog transmission digital transmission HART communication Transmission specification 4 20mADC linear load resista...

Страница 52: ......

Страница 53: ......

Страница 54: ......

Страница 55: ...ower explosive limit LEL of the combustible gas to be detected is set to 100 vol A unit used to express the percentage of a specific substance or gas in a volume of solution Calibration Adjusts the re...

Страница 56: ...Revision Date issued 0 First edition 11 10 2020 1 P9 Safety information Declaration of Conformity P53 Added CH4 0 100vol to the list of gases to be detected MED specification P55 Added vol to the defi...

Страница 57: ......

Отзывы: