2 Maintenance Mode
- 5 -
SC-8000
BUMP
Press the ENTER switch.
The bump test gas concentration is displayed.
The concentration of the prepared test gas must
be consistent with the displayed test gas
concentration.
To change the test gas concentration value,
change the value in span adjustment menu. The
test gas concentration is set to the same value as
the span gas concentration. Automatic span
adjustment => P15
Supply the test gas and press ENTER.
BUMP and APPLY are displayed alternately, and
the countdown is started.
Supply test gas
Goes to (1) when passed or
(2) when failed after countdown
(1)
<When passing the test>
The result is displayed after the countdown finishes.
Stop supplying the test gas. The results and values
are displayed alternately every time the
▲
or
▼
switch
is pressed.
P: Pass, F: Fail
Stop supplying
test gas
After checking the result, press ENTER. The gas
monitor returns to the maintenance mode menu.
Return to BUMP.