11.PRODUCT SPECIFICATIONS
11−1.Specifications
Applicable detector head
General measuring signal instrument
Gas concentration display
LED(4digits・7segments)
Power indication
PW/TR lamp lighting(green)
Gas alarm type
Two-level alarm(H-HH or L-H, L-LL)
Gas alarm indication
1st:AL1 lamp blinking or lighting(orange)
2nd:AL2 lamp blinking or lighting(red)
Gas alarm action
Latched or Non-latched, Lock-in
Gas alarm contact
Each no-voltage contact 1a or 1b(contact output for each alarm)
Non-exciting at normal(exciting at alarm) or exciting at normal(non-exciting at
alarm)
Trouble alarm Self diagnosis
System failure/Detecting circuit failure
Trouble alarm indication
PW/TR lamp blinking/Indicates error codes
Trouble alarm action
Auto-recover
Trouble alarm contact
No-voltage contact 1a or 1b
Non-exciting at normal(exciting at alarm) or exciting at normal(non-exciting at
alarm)
Contact capacity
AC100V・0.5A/DC30V・1.5A(load resistance)
Transmission scheme
Analog transmission
Specification of transmission
DC4〜20mA(non-isolated・load resistance less than 300Ω)
Gas detector head signal
DC4〜20mA
Cable between detector
CVVS worth of shield cable・2-core
Various functions
Alarm delay/Peak hold/Alarm trend history
Power supply
DC24V±10%
Power consumption
MAX.5W(MAX.8VA by using Multi case)
Initial clear
Approx.25sec
Operating temperature
0〜40℃(non-rapidly-vary)
Operating humidity
10〜90%RH(non-condensing)
Structure
Housing type for the case
front identification card type(put into Single case or Multi case)
Outer dimension
Approx.36(W)×72(H)×134(D)mm
Weight
Approx.0.10kg(unit only)
11−2.Product composition
Standard compositions
・Indicator/alarm unit Model RM-592
・Operating instruction manual…1 vol.
・Spare fuse…Depends on ordered quantity of the unit.
1〜10 units
11〜20 units
21〜50 units
51 units and above
1 pce
2 pcs
3 pcs
4 pcs