2-2. Operation List of Status Data (address40001)
6
2-2. Operation List of Status Data (address40001)
●:
Bit ON
○:
Bit OFF
-:
Unsettled
※
In H-HH/L-LL alarm type :
●
In L-H alarm type :
○
NOTES:
*1 In maintenance mode, the alarms do not work even if the gas concentration gets over the alarm
point.
*2 In maintenance mode, the gas concentration could be minus. When alarm process is activated by
gas concentration data, make a design with consideration of negative value (complete
representation).
*3 The gas concentration becomes an integer which maintains the number of significant digits.
Examples)
①
If the gas concentration is 20.9 in full scale 25.0
→
209
②
If the gas concentration is 0.2 in full scale 50.0
→
2
③
If the gas concentration is 0.20 in full scale 5.00
→
20
S t a t u s
1
5
1
4
1
3
1
2
11
1
0
9
8
7
6
5
4
3
,
2 1
,
0
mainte
nanc
e
Te
st
Inhib
it
Initial
Ran
ge ov
er
Smoke(SiO2)
2nd Alarm
1st Alarm
T
roub
le :
senso
r
Unus
ed
T
rouble : flow
Information of
dou
ble ra
ng
e
Unit Cod
e o
f
gas conce
ntratio
n
Decima
l Co
de
Normal :
Measuring
○ ○ ○
○
○
○
○
○
○
○
○
○
-
-
Alarm : 1st
○ ○ ○
○
○
○
○
●
○
○
○
○
-
-
Alarm : 2
nd
○ ○ ○
○
○
○
●
※
○
○
○
○
-
-
Alarm : Smoke
○ ○ ○
○
●
●
●
●
○
○
○
○
-
-
F.S. over
○ ○ ○
○
●
○
-
-
○
○
○
○
-
-
Constant time
after power on
(or after reboot)
○ ○ ○
●
○
○
○
○
○
○
○
○
-
-
Maintenance
● ○ ○
○
-
○
-
-
○
○
○
○
-
-
Alarm Test
● ● ○
○
-
○
-
-
○
○
○
○
-
-
Trouble : Sensor
○ ○ ○
○
○
○
○
○
●
○
○
○
-
-
Trouble : Flow
○ ○ ○
○
○
○
○
○
○
○
●
○
-
-
Measuring of L
side
○ ○ ○
○
○
○
○
○
○
○
○
●
-
-
Inhibit
● ○ ●
○
○
○
○
○
○
○
○
○
-
-