2-1. RM-5000 Modbus Register Map
5
Address Item
Content
40017 Digit
Signed integer
Significant figures of digit which is made to integer. Actual
digit is calculated by multiplying this integer by bit 0 to 1 of
address 40001 or 40018.
40018
Decimal Point Position
0: actual size, 1: one tenth, 2: one hundredth, 3: one thousandth
40019
Unit
0: vol%, 1: %LEL, 2: ppm, 3: ppb
40020
X 10 Scale Information
Information of ten times measuring range(H side and single
range)
Address 40012: Full scale value, Address 40013: 1st alarm point,
Address 40014: 2nd alarm point, address 40015: convert peak
value by ten times.
40021
~
40025
Gas Name
Gas name = ASCII code 10 letters
40026
Full Scale Value in L side
Signed integer: L side full scale in double range
Significant figures of L side full scale which is made to integer.
Actual L side full scale is calculated by multiplying this integer by
bit 0 to1 of address 40028.
40027
L side Digit
Signed integer: L side digit in double (W) range
Significant figures of L side digit which is made to integer. Actual L
side digit is calculated by multiplying this integer by bit 0 to 1 of
address 40028.
40028
Decimal Point Position in L
side
Position of L side decimal in double (W) range
0: actual size, 1: one tenth, 2: one hundredth, 3: one thousandth
40029
L side Unit
L side Unit in double (W) range
0: vol%, 1: %LEL, 2: ppm, 3:ppb
40030
x10 Scale Information in L
side
Information of ten times measuring range (L side in double (W)
range)
Address 40026: full scale value, Address 40013: 1st alarm,
Address 40014: 2nd alarm, Address 40015: convert peak value by
ten times
40031
Concentration Value of H
(High) side in case of double
(W) range
Signed integer: Concentration value of H (High) side in case of
double (W) range
Significant figures of concentration of H side which is made to
integer. Actual concentration of H side is calculated by multiplying
this integer by bit 0 to 1 of address 40001 or 40018.
40032
AMP Types
0: GP, 1: NC, 2: NCW, 3: OX, 4: GH, 5: HART, 6: SC