5 How to Operate
5-3. How to start the detector
SD-1DGH-AS
- 30 -
NOTE
The semiconductor sensor used in the detector must be warmed up for a specified warm-up (powered)
time after power is supplied. The required warm-up (powered) time depends on the unpowered time for
the sensor. The time shown in the table shown below must be met.
Unpowered time
Guidelines for warm-up
(powered) time
24 hours or less
4 hours or more
72 hours or less
24 hours or more
10 days or less
2 days or more
Less than 1 month
7 days or more
Less than 3 month
14 days or more
3 months or more
1 month or more