6.6 The receiver optical unit exposure to direct sunlight, powerful light sources 

or other infrared radiation sources should be excluded.

6.7 Several IPDL-Ex with parallel monitored zones may be installed in a single 

premise, opposite operation of neighboring receivers and transmitters is permitted. 
Whereupon distances between two neighboring IPDL-Ex must be maximum 9 m 
and minimum:

a) 5 m – if the distance between the TM and the RM is 50 to 150 m;
b) 2.5 m – if the distance between the TM and the RM is 8 to 50 m.
6.8 The IPDL-Ex should be installed at 0.3 to 0.6 m distance from ceilings. In case 

the premise height is greater than 12 m, the IPDL-Ex should be installed in two tiers.

6.9 IPDL-Ex Installation Procedure:
- mark out the TM and the RM installation points at the same distances from 

the ceiling and the nearest wall or beam (the angle between the TM and the RM 
base planes must not exceed 6.5 degrees);

- remove covers from modules by pressing the latches with a screwdrivers 

through an opening near the LED indicator and simultaneously pulling the cover 
away;

- fasten the TM and the RM bases tightly to the wall or timber without changing 

positions of optical units;

- connect power supply lines and Al1 and Al2 alarm loops to the TM and the 

RM terminal blocks;

- if necessary, connect the OAED to the TM («+K

»

 connect to «+OAED

»

,  

«-K

»

 – to «-OAED

»

).

6.10 Depending on the alarm loop power supply circuit, set the switch «P»  

located on the TM PCB in the following positions:

- DIP-switch 2 «P

»

 in ON position – normally opened Al2;

- DIP-switch 2 «P

»

 in OFF position – normally closed Al2.

6.11 Adjust the operating threshold needed for the premise by means  

of 3, 4 DIP-switches «THRESHOLD

»

 as per Table 4. In case IPDL-Ex is installed in 

premises with gassed air (in garages, hot shops, etc.), the threshold value should 
be increased, and vice versa, in the gas free premises where low concentration 
of smoke is an attribute of a fire the threshold should be reduced.

7 IPDL-Ex Adjustment

7.1 The IPDL-Ex constancy of performance largely depends on it’s adjustment, 

therefore, it should be performed especially thoroughly.

7.2 Firstly, the TM and the RM EI optical units axes should be aligned as close 

as possible by means of their adjustment.

7.3 Adjust the RM optical unit in the following way:
- put 1 and 2 DIP-switches on the RM PCB in the positions corresponding to the 

distance between the TM and the RM (the positions of DIP-switches depending 
on the distance are listed in Table 3);

- look in the mirror located at the top of the TM base and change the sight angle 

until the cross (the point on the mirror) is superimposed onto the image of the RM;

- superimpose the sight of the TM optical unit onto the cross without changing 

the vertical and the horizontal sight angles with adjustment screws;

- the optical diagram of adjustment is shown in Figure 2.
7.4 Execute the RM adjustment:
- look in the mirror located at the top of the RM base and change the sight angle 

until the cross (the point on the mirror) is superimposed onto the image of the TM;

- superimpose the sight of the RM optical unit onto the cross without changing 

the vertical and the horizontal sight angles with adjustment screws;

- any foreign objects and IR radiation sources (space heaters, welding units, 

etc.) emergence in the IPDL-Ex operation zone during adjustment procedure  
IS PROHIBITED;

- energize the IPDL-Ex;
- set «A

»

 DIP-switch 1 in he ON position - the RM turns to adjustment mode;

- monitor the signal level by HL1 – HL5 LED indicator:
- red HL1 LED indicator lighting means no signal;
- green HL2 – HL5 LED indicators lighting display signal level (the stronger the 

signal, the more indicators are lighting);

- frequent blinking of all HL2 – HL5 indicators means that the signal is above 

normal at minimum gain level – it is possible in case the TM transmission power 
is incorrectly chosen or the distance between the TM and the RM is too small;

- achieve the maximum signal level (indicated by the number of lit HL2 – HL5 

indicators) by means of adjusting screws;

- the signal level may be evaluated more precisely by readings of a voltmeter 

connected to the «-K+

»

 terminal block, whereupon the readings should be as close 

to IPDL-Ex power supply voltage as possible;

- for fine adjustment after performing the two previous steps, the TM adjustment 

should be repeated and the maximum signal level obtained with the help of 
adjusting screws;

- close the TM cover and return to the RM adjustment;
- put DIP-switch 1 «A» into the OFF position, whereupon the IPDL-Ex is finishing 

adjustment and assigns the time for installing the cover and fine adjustment with 
regard for signal loss with the light filter;

- the time allowed for the cover installation is displayed by means of the HL1 

LED indicator: for 35 s, HL1 blinks at 4 Hz frequency, then for 15 s, at 10 Hz, 
during this time, the IPDL-Ex cover should be installed;

- upon expiry of the time allowed, the RM completes adjustment and switches 

to a standby mode displayed by HL1 LED blinking at 5 s intervals;

- it is prohibited to de-energize IPDL-Ex and to cover  the transmitter and the 

receiver lenses during the period of time from the moment of the cover  installation 
till the IPDL-Ex changes to a standby mode. Presence of foreign objects into the 
IPDL-Ex operation zone should be excluded as well;

- after IPDL-Ex changes to a standby mode, it’s adjustment is considered to 

be completed.

8 Functional Check

8.1 IPDL-Ex parameters in a «Fire» message generation mode are tested at 

the factory or at specialized laboratories with the application of special technical 
facilities during fire tests. IPDL-Ex functional check in the «Fire» message generation 
mode should be performed after IPDL-Ex adjustment. under the TM cover removed. 
Press and hold down the «TEST» key button on the TM PCB or press and hold 
down a «TEST» key button on the TM «TEST» terminal block (in this case, the TM 

lid  may stay in it’s position). The key button should be held down for at least 5 s, 

whereupon the TM HL1 LED indicator should light continuously. BRSS-Ex should 
receive a «Fire» alarm message.

8.2 Functional check of IPDL-Ex in a «Fault» message generation mode is  

performed as follows.

In case the TM «TEST» key button is held down for more than 10 s, the TM 

switches to the fault simulation mode. The TM HL1 indicator blinks at 1 s intervals, 
whereupon the RM HL1 indicator also should start blinking at 1 s intervals. A 
control panel should receive a «Fault» message. After the TM «TEST» key button 
is released, the IPDL-Ex returns to standby mode.

9 Manufacturer’s Guarantees

9.1 The manufacturer guarantees conformity of the IPDL-Ex to the specifications 

provided the transportation, storage, installation and operation conditions are 
observed.

9.2 The guaranteed shelf life of an IPDL-Ex is 24 months since the date of 

manufacture. The guaranteed useful life is 18 months since the day of putting into 
operation within the guaranteed shelf life.

9.3 An IPDL-Ex that is found non-conforming to the requirements of specifications 

should be repaired by the manufacturer, provided the transportation, storage 
conditions, as well as installation and operation rules have been complied with.

10 Transportation and Storage

10.1 An IPDL-Ex in original transportation package may be transported by any 

means of transportation in closed vehicles (railway wagons, closed motor vehicles, 
sealed and heated airplane compartments, vessel holds, etc.) over all distances.

When transporting IPDL-Ex, the rules and regulations applicable to various 

means of transportation must be adhered.

10.2 Storage premises must not contain any current-conducting dust, acid and 

alkali fumes, as well as corrosive gases or those destroying insulation.

11 Packing Certificate

Linear smoke detector «IPDL-Ex» has been manufactured in compliance with 

the active technical documentation and classified as fit for operation and packed 
by «RIELTA» JSC.

Packing date _____________________________

month, year 

  

12 Claims

In case an IPDL-Ex is found non-complying to the specifications, or in case of 

a breakdown during the guarantee period, the IPDL-Ex must be returned to the 
manufacturer with the datasheet attached.