49
TECHNICAL ASSISTANCE SERVICE
− Press the
T
key
− With an outdoor temperature sensor con-
nected, set the room temperature setpoint.
This setting affects the shifting of the he-
ating curves (see the second figure on
page"Attenuated outdoor temperature" a
pagina 48).
− With no outdoor temperature sensor con-
nected, set a fixed boiler temperature
setpoint.
Press the
+
-
keys to adjust the setpoint.
Press any of the keys to exit:
R
T
M
V
.
The new setting is stored in memory.
In the same way, set parameter 5 to "User" to set the
"reduced room temperature setpoint" or "reduced boi-
ler setpoint".
Parameter 555-b2 lets you specify whether a room
thermostat or a timer-thermostat is connected to the
"TA" terminals.
In the first case (room thermostat), the boiler switches
off when the contacts open.
In the second case (timer thermostat) the reference
curve will be that determined by the reduced room
temperature setpoint that has just been set.
SETTING CENTRAL HEATING PARAMETERS
If a remote storage cylinder (accessory) is present, con-
nect the storage cylinder temperature sensor to the
control panel and set the manufacturer level parameter
“558b2”=0 (see the “Manufacturer level” section).
Press the
R
key.
Press the
+
-
keys to adjust the DHW setpoint.
Press any of the keys to exit:
R
T
M
V
.
The new setting is stored in memory.
SETTING DOMESTIC HOT WATER PARAMETERS