Setting functioning parameters
If an outdoor temperature sensor is connected, the controller uses the heating curve to generate the CH flow tempera-
ture setpoint, thus enabling the boiler to maintain a constant room temperature even without the use of a room unit.
The steeper the slope of the heating curve, the higher the flow temperature setpoint at low outdoor temperatures (see
Manufacturer parameter 532).
20
30
40
50
60
70
80
90
S=2
S=10
S=20
Tm
Tec
-20
-15
-10
-5
0
5
10
15
20
Heating curves with room temperature setpoint = 20°C
Tm
CH flow temperature
Tec
Compound outdoor
temperature
S Slope
If the room setpoint is reduced, these curves shift downwards.
Sa=10°C
Sa=20°C
20
30
40
50
60
70
80
90
-20
-15
-10
-5
0
5
10
15
20
Tec
Tm
Sa=30°C
Heating curve with slope = 15
Tm
CH flow temperature
Tec
Compound outdoor
temperature
Sa
Room temperature setpoint