![Riello RX 1000 S/PV Скачать руководство пользователя страница 54](http://html1.mh-extra.com/html/riello/rx-1000-s-pv/rx-1000-s-pv_installation-use-and-maintenance-instructions_1460066054.webp)
20079424
52
GB
Maintenance
Combustion
In case the combustion values found at the beginning of the inter-
vention do not respect the standards in force or, in any case, do
not correspond to a proper combustion, contact the Technical As-
sistance Service in order to carry out the necessary adjustments.
Tab. M
8.3
Opening and closing the burner
MIN output
MAX output
CO
2
(%)
O
2
(%)
CO
2
(%)
O
2
(%)
Methane
8
6.6
8.5
5.7
LPG
9.5
6.4
10
5.6
G25
7.8
6.8
8.3
5.8
DANGER
Turn off the burner's power supply using the main
system switch.
DANGER
Turn off the fuel interception tap.
Wait for the components in contact with heat
sources to cool down completely.
After carrying out maintenance, cleaning or
checking operations, reassemble the cover and
all the safety and protection devices of the burner.
Содержание RX 1000 S/PV
Страница 2: ...Translation of the original instructions...
Страница 81: ......
Страница 82: ......
Страница 83: ......