![Riello RX 1000 S/PV Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/riello/rx-1000-s-pv/rx-1000-s-pv_installation-use-and-maintenance-instructions_1460066024.webp)
20079424
22
GB
Installation
5.7
Fuel supply
The burners are teamed with one-piece pneumatic proportioning
gas valves, via which the amount of gas delivered, and hence the
output produced, can be modulated.
A signal reporting pressure detected in the air circuit is carried to
the pneumatic gas valve, which delivers an amount of gas in pro-
portion to the airflow produced by the fan.
Air/gas mixer
Gas and combustive air are mixed inside the purging circuit (mix-
er), starting from the intake inlet.
Through the gas train, fuel is introduced into the intake air current
and optimal mixing commences with the aid of a mixer.
NOTE:
The compensation pipe (T) between the valve-Venturi allows
compensation to occur for accidental blockage of the suc-
tion line due to a reduction in the gas delivered.
5.7.1
Gas train
This has been type-approved together with the burner, in accord-
ance with regulation EN 676, and is supplied as standard
(Fig. 23).
Key (Fig. 23)
1
Gas input pipe
2
Manual valve
3
Vibration damping joint
4
Pressure gauge with push-button cock
5
Valve including:
- filter (replaceable)
- working valve
- pressure adjuster
P1-
Pressure upline of the filter
P2
Downstream pressure of valve
L -
Gas train supplied
L1 -
The responsibility of the installer
Explosion danger due to fuel leaks in the pres-
ence of a flammable source.
Precautions: avoid knocking, attrition, sparks and
heat.
Make sure the fuel interception tap is closed be-
fore performing any operation on the burner.
WARNING
The fuel supply line must be installed by qualified
personnel, in compliance with current standards
and laws.
Gas valve
Metallic protective device
Air/gas mixer
in the circuit
of the suction line
Minimum gas flow adjustment (V2)
20075337
Electronic valve
Maximum
Compensation pipe (T)
connection (XV1)
Fig. 22
Quick Coupling
Compensation pipe (T)
gas flow adjustment (V1)
Downstream pressure test point
L1
L
VS
VR
R
F
1
2
3
4
5
P2
P1
D8668
Fig. 23