14

GENERAL

DESCRIPTION

RTQ 3S

91(*)

115(*)

166(*)

217(*)

255(*)

318(*)

349(*)

Fuel

GAS

Rated heat input 

min

70

90

115

166

217

255

318

kW

max

90

115

166

217

255

318

348

kW

Rated useful heat output Pn

min

66,9

86,6

110,4

159,2

208,8

244,3

304,0

kW

max

84,8

110,2

158,7

206,8

243,0

303,4

332,0

kW

Useful efficiency at minimum Pn

95,6

96,2

96,0

95,9

96,2

95,8

95,6

%

Useful efficiency at maximum Pn

94,2

95,8

95,6

95,3

95,3

95,4

95,4

%

Useful efficiency at 30% max. Pn

95,9

95,1

95,6

96,3

96,5

96,5

96,7

%

Constant pressure drop

< 1,5

< 1,4

< 1,2

Flue gas temperature (∆T)

 93

 95 ÷ 108

°C

Flue gas mass flow rate

0,040

0,050

0,072

0,094

0,111

0,139

0,151

kg/sec

Furnace pressure

2,0

1,5

1,3

2,2

2,8

3,2

3,9

mbar

Furnace volume

97,4

91,0

138,4

199,1

199,1

298,9

298,9

dm3

Total volume of flue gas side

139,7

163,2

234,3

317,2

325,6

457,9

457,9

dm3

Total surface area for heat exchange

3,62

4,35

6,68

8,59

9,47

12,34

12,34

m2

Volumetric heat load

928

1264

1199

1090

1281

1064

1164

kW/m3

Specific heat load

24,1

25,2

23,8

24,1

25,7

24,6

26,9

kW/m2

Maximum operating pressure

6

bar

Maximum admissible temperature

110

°C

Maximum operating temperature

95

°C

Min. admissible water return temp.

50

55

°C

Pressure drop ∆T 10°C

42,0

15,1

42

76,5

144

148

162

mbar

Pressure drop ∆T 20°C

14,0

3

11,2

17,2

45

27,2

29,7

mbar

Water capacity

126

161

191

268

258

308

308

litri 

Turbulators 

22

22

30

34

39

44

44

(*) Heating appliance marketed before 1 January 2018, intended exclusively for replacement under the terms of EU
    Regulation 813/2013, article 1, section 2, letter (g).

Technical data for boilers with gas burners <400 kw

TECHNICAL DATA FOR BOILERS WITH GAS BURNERS <400 KW

Содержание RTQ 1100 3S

Страница 1: ...1 INSTALLATION OPERATION MAINTENANCE AND SYSTEM MANAGEMENT MANUAL S T E E L B O I L E R S RTQ 3S...

Страница 2: ...0024200 RTQ 115 3S 4032606 0 RTQ 166 3S 4032607 0 RTQ 217 3S 4032608 0 RTQ 255 3S 4032609 0 RTQ 318 3S 4032610 0 RTQ 349 3S 4032611 0 RTQ 448 3S 4032613 0 RTQ 511 3S 4032614 0 RTQ 575 3S 4032615 0 RTQ...

Страница 3: ...larly by an authorised r Technical Assistance Centre Their personnel are specially trained to keep your boiler efficient and cheap to run Technical Assistance Centres also stock any original spare par...

Страница 4: ...boilers 400 kw 15 SYSTEM MANAGER 16 Start up 16 Temporary shutdown 17 Preparing for extended periods of disuse 18 Cleaning 18 Maintenance 19 Useful information 19 HEATING ENGINEER 20 Unpacking the pr...

Страница 5: ...e boiler even if it is sold to another owner or transferred to another user or to another installation If you damage or lose this manual order a repla cement immediately from your local r Technical As...

Страница 6: ...oad optimises the efficiency of the boiler burner system The boiler body is thoroughly insulated with a layer of high density glass wool The boiler s front door and the flue gas box can be ope ned com...

Страница 7: ...ressure measurement cooling valve 3 Door 4 Casing 5 Central heating return 6 Safety device fitting 7 Instrument bulb sensor sockets 8 Central heating flow 9 Flue gas pipes 10 Turbulators 11 Combustion...

Страница 8: ...Immersion temperature sensor 1 1 1 1 Solar collector temperature sensor 1 Pipe temperature sensor 1 1 CLIMA COMFORT STANDARD Control by control panel with assistance of accessories listed below ACCES...

Страница 9: ...Z t l 3470311 RL 44 MZ t l 3470341 R RL 50 t l 3474633 RL 50 t l 3474633 4031395 RL 70 t l 3475033 RL 100 t l 3475233 RL 130 t l 3475433 RL 190 t c 3475613 3010444 RL 250 t c 3470010 3010422 RL 300 B...

Страница 10: ...ation on Burner installation Electrical connections Burner adjustments b 1 Long heads and burner plates are required for the correct installation and coupling of the burners 2 If a two stage burner is...

Страница 11: ...R INSTALLATION Before fixing the burner to the boiler make sure that The door opens the right way see the relevant sections for details on how to reverse the door The length L of the burner fixing bol...

Страница 12: ...rra obbligatorio Raccordement la terre obligatoire PER CATEGORIA COMBUSTIBILE E PAESI DI DESTINAZIONE VEDI ETICHETTA BRUCIATORE POUR CATEGORIE COMBUSTIBLE ET PAYS DE DESTINATION VOIR ETIQUETTE BRULEUR...

Страница 13: ...LCV 90 1 95 6 90 7 96 2 90 5 96 0 90 4 95 9 90 7 96 2 90 3 95 8 90 1 95 6 Efficiency at rated heat input in low tem perature mode h1 with return at 37 C HCV LCV 94 0 99 7 94 0 99 7 94 0 99 7 94 0 99 7...

Страница 14: ...1 199 1 298 9 298 9 dm3 Total volume of flue gas side 139 7 163 2 234 3 317 2 325 6 457 9 457 9 dm3 Total surface area for heat exchange 3 62 4 35 6 68 8 59 9 47 12 34 12 34 m2 Volumetric heat load 9...

Страница 15: ...erature T 95 108 C Flue gas mass flow rate 0 206 0 222 0 250 0 277 0 332 0 392 0 477 0 553 0 704 0 911 1 050 kg sec Furnace pressure 3 5 4 2 3 4 4 5 5 3 6 0 3 3 5 3 4 7 5 1 7 6 mbar Furnace volume 410...

Страница 16: ...as cock and heating water cock are open While the system is still cold check that working pres sure in the water circuit is over 1 bar but below the maximum limit specified for the boiler If the syste...

Страница 17: ...ed button light on the bur ner and wait until the flame ignites Repeat this operation 2 3 times at the most If the pro blem persists after that call r s Technical Assistance Service If you need to shu...

Страница 18: ...f there is any risk of freezing b Contact r Technical Assistance Service if you encounter any problems in completing the above procedure Use a cloth damped in soapy water to clean the boiler s externa...

Страница 19: ...ANCE AND COMBUSTION EFFICIENCY MEASUREMENTS r s Technical Assistance Service is qualified to satisfy these legal requirements and can also provide useful information on MAINTENANCE PROGRAMMES designed...

Страница 20: ...arts catalogue b The instruction manual is an integral part of the boiler Once located read it thoroughly and keep it safe 2 THE CASING PANELS complete with assembly accessories 2 packs for models RTQ...

Страница 21: ...975 mm A1 Base width 660 753 803 875 875 925 925 mm B Depth 1060 1130 1305 1480 1480 1710 1710 mm B1 Base depth 882 945 1110 1255 1255 1450 1450 mm C Height 740 790 840 980 980 1030 1030 mm D Burner a...

Страница 22: ...300 1600 2100 2400 A Width 1150 1150 1220 1220 1285 1360 1450 1535 1610 1715 1715 mm A1 Base width 1100 1100 1170 1170 1235 1310 1400 1485 1555 1660 1660 mm B Depth 2040 2040 2310 2310 2450 2765 3030...

Страница 23: ...mm above floor level aDo not install the boiler outdoors It is not designed to work outdoors and is not fitted with the necessary automatic anti frost systems to do so RTQ 91 3S MODELS ONLY r RTQ 3S b...

Страница 24: ...must also be as straight as possi ble sealed insulated and not blocked or choked Make sure that the electrical system has been installed by a qualified electrician in compliance with applicable stand...

Страница 25: ...2 1 2 G2 1 2 G2 1 2 G2 1 2 DN80 DN80 DN100 DN100 DN100 DN125 DN125 DN125 DN150 DN175 DN175 5 Condensate drain G1 2 G3 4 G3 4 G3 4 G3 4 G3 4 G3 4 G1 G1 G1 G1 G1 G1 G1 G1 G1 G1 G1 6 Boiler drain G1 1 4...

Страница 26: ...S 1 Boiler 2 System headers 3 Sectioning valves 4 System circulators 5 Check valves 6 Automatic pressure relief valve 7 Boiler safety valve 8 Boiler discharge valve 9 Expansion tank 10 Pressure reduce...

Страница 27: ...ues Schematic diagram central heating and domestic hot water production RTQ 115 2400 3S REFERENCE VALUES PH 6 8 Electrical conductivity below 200 S cm 25 C Chlorine ions below 50 ppm Sulphuric acid io...

Страница 28: ...755 820 865 900 1000 1000 H2 1010 H 0 30 60 90 H H2 Typical installation schematic Typical installation schematic RTQ 91 3S RTQ 115 2400 3S D 3 5 D b A sensor socket must be positioned at a distance...

Страница 29: ...ws 1 2 4 5 3 1 6 8 7 Make sure that the main door fixing bolts 1 are securely tightened Remove the top safety bolts 2 and the door stop bracket 3 Remove the bottom safety bolts 4 and the door stop bra...

Страница 30: ...uipment Once the bolt 6 has engaged its hole re tighten the door fixing bolts 1 Fit the top door stop bracket 3 to the opposite side of the door and fix it in place with the safety bolts 2 Fit the bot...

Страница 31: ...adequate size and complies with legislation in the country of installation Fit the nut and washer 1 to the earth terminal and tighten the nut Connect the other end of the cable to the system s earth...

Страница 32: ...n instruction manual Route the electrical cables and insert the bulbs sensors in their sockets Fit the cable grommets provided into their seats in the panels Fit the top panel 4 to close the top of th...

Страница 33: ...nd rear heads Secure the side panels in place with the top cross beam 3 and the screws provided Fit your chosen control panel on the top panel 4 as instructed in the control panel s own instruction ma...

Страница 34: ...with the top cross beam 3 and the screws provided Fit the top panel 4 Fit your chosen control panel on the top panel 5 as instructed in the control panel s own instruction manual Route the electrical...

Страница 35: ...to the central top panel 9 for models up to RTQ 1600 3S or on one of the side panels 2 for models RTQ 1300 1600 2100 2400 3S as instructed in the control panel s own instruction manual Route the elect...

Страница 36: ...the heat exchanger The water and gas cocks are open There is an adequate fuel supply The expansion vessel is properly charged The working pressure in the water circuit is over 1 bar but below the maxi...

Страница 37: ...uld now ignite and remain in operation until the set temperature is reached If any ignition faults or malfunctions occur the burner performs a LOCKOUT SHUTDOWN This is shown by the red button light on...

Страница 38: ...the main power switch to the boiler and make sure that the boiler shuts down properly Provided all the above conditions are satisfied start the boiler up again then analyse the combustion fumes measur...

Страница 39: ...door These bolts are captive in the door and can not be removed b bThe first time you open the door remove the spare hinge assembly B bushing 10 bolt 9 and washer 11 opposite the hinged side of the do...

Страница 40: ...u are using fuel oil burners with a smoke scale reading higher than 3 perform the following actions every 300 hours of operation Clean the boiler s heat exchange surfaces Check and clean the turbulato...

Страница 41: ...er dirty Clean the flue gas pipes Boiler and burner mismatched Check specifications and settings Insufficient air fuel flow to burner Check and adjust the burner Control thermostat problem Check the f...

Страница 42: ...g Fumes escaping into the air There is a smell of fumes Clean the boiler body Clean the flue gas pipes Check that the boiler flue gas pipes and stack are all properly sealed Check the door seal Circui...

Страница 43: ...43 TECHNICAL ASSISTANCE SERVICE...