20068423
56
GB
Faults - Probable causes - Solutions
Bit 4
Valence
16
Deviation of section compared with the last reference
Overloading of the servomotor or servomotor subjected to
mechanical torsion.
1. Check if the servomotor is blocked in any point along its
range of action.
2. Check if the torque is sufficient for the application.
90 - 91
#
Burner internal checking error
93
#
Flame signal acquisition error
3
Short circuit of the sensor
Short circuit in the QRB sensor...
1. Check the wiring.
2. Flame detector probably faulty.
95
#
Relay supervision error
3 Ignition transformer
4 Fuel valve 1
5 Fuel valve 2
6 Fuel valve 3
External power supply - Contact active
Check the wiring
96
#
Relay supervision error
3 Ignition transformer
4 Fuel valve 1
5 Fuel valve 2
6 Fuel valve 3
The relay contacts have joined together
Check the contacts:
1. Control box connected to the power supply: the fan output
must be without voltage.
2. Disconnect the power supply. Disconnect the fan. The
resistive connection between the fan output and the neutral
wire is not allowed.
If one of the 2 tests fails, replace the control box because the
contacts are definitively joined together and it is no longer
possible to guarantee safety.
97
#
Relay supervision error
0
The safety relay contacts have joined together or the
safety relay has been powered by an external power
supply
Check the contacts:
1. Control box connected to the power supply: the fan output
must be without voltage.
2. Disconnect the power supply. Disconnect the fan. The
resistive connection between the fan output and the neutral
wire is not allowed.
If one of the 2 tests fails, replace the control box because the
contacts are definitively joined together and it is no longer
possible to guarantee safety.
98
#
Relay supervision error
2 – Safety valve
3 Ignition transformer
4 Fuel valve 1
5 Fuel valve 2
6 Fuel valve 3
The relay does not start up
Carry out a reset; if the error arises repeatedly, replace the unit
99
#
Relay internal checking error
Carry out a reset; if the error arises repeatedly, replace the
control box
3
Relay internal checking error
Carry out a reset; if the error arises repeatedly, replace the
control box
Software version V03.10: If error C:99 D:3 occurs during the
standardisation of the VSD, temporarily deactivate the Alarm
function at the start of the pre-purging phase (parameter 210 =
0) or interrupt the signal controller-ON
100
#
Relay internal checking error
Carry out a reset; if the error arises repeatedly, replace the
control box
105
#
Contact sampling internal error
0 Min. pressure switch
1 Max. pressure switch
2 Valve operation test
pressure switch
3 Air pressure
4 Load controller open
5 Load controller on/off
6 Load controller closed
7 Safety loop / burner flange
8 Safety valve
9 Ignition transformer
10 Fuel valve 1
11 Fuel valve 2
12 Fuel valve 3
13 Reset
Blocked upon irregularity
Can be caused by capacitive loads or presence of DC voltage
on the main power supply of the control box. The diagnostic
code indicates the input in which the problem arose
106 ÷ 108
#
Contact request internal error
Carry out a reset; if the error arises repeatedly, replace the
control box
110
#
Voltage monitoring test internal error
Carry out a reset; if the error arises repeatedly, replace the
control box
Error
code
Diagnostic code
Meaning of the REC 27.100A2 system
Recommended measures