20068423
54
GB
Faults - Probable causes - Solutions
2
Valve leak detection test not possible
The valve leak detection is active, but the minimum gas
pressure switch is selected as input for X9-04 (check
parameters 238 and 241)
3
Valve leak detection test not possible
The valve leak detection is active, but no input has been
assigned (check parameters 236 and 237)
4
Valve leak detection not possible
Valve leak detection is active, but 2 inputs have already been
assigned (configure parameter 237 or maximum gas Pressure
switch or POC)
5
Valve leak detection not possible
The valve leak detection is active, but 2 inputs have been
assigned (check parameters 236 and 237)
14
#
POC
0
POC Open
Check if the closure contact of the valve is closed
1
POC Closed
Check the wiring
Check if the closure contact of the valve opens when the valve
is checked
64
POC Open - Alarm lockout at start
Check the wiring
Check if the closure contact of the valve is closed
19
80
Fuel pressure, POC - Alarm lockout at start
Check that the pressure switch is closed when no pressure is
present from the fuel
Check that there are no short-circuits
20
#
Pmin
0
Minimum gas/oil pressure absent
Check that there are no line interruptions
1
Scarcity of gas - Alarm lockout at start
Check that there are no line interruptions
21
#
Pmax/POC
0
Pmax: Max. gas/oil pressure exceeded
POC: POC open (software version
V02.00)
Check the wiring.
POC: check if the closure contact of the valve is closed
1
POC closed (software version
V02.00)
Check the wiring.
Check if the closure contact of the valve opens when the valve
is checked
64
POC Open - Alarm lockout at the start (software version
V02.00)
Check the wiring.
Check if the contact of the valve opens when the valve is
checked
22
OFF S
#
Safety circuit/Burner flange
0
Safety circuit open /Burner flange open
1
Safety circuit open /Burner flange open - Alarm lockout at
start
3
Safety circuit open /Burner flange open, extraneous light -
Alarm lockout at start
5
Safety circuit open /Burner flange open, extraneous light -
Alarm lockout at start
17
Safety circuit open /Burner flange open, extraneous light -
Alarm lockout at start
19
Safety circuit open /Burner flange open, extraneous light -
Alarm lockout at start
21
Safety circuit open /Burner flange open, extraneous light -
Alarm lockout at start
23
Safety circuit open /Burner flange open, extraneous light,
air pressure, fuel pressure - Alarm lockout at start
65
Safety circuit /Burner flange open, POC - Alarm lockout at
start
67
Safety circuit open /Burner flange open, extraneous light,
POC - Alarm lockout at start
69
Safety circuit open /Burner flange open, air pressure, POC
- Alarm lockout at start
71
Safety circuit open /Burner flange open, extraneous light,
air pressure, POC - Alarm lockout at start
81
Safety circuit open /Burner flange open, fuel pressure,
POC - Alarm lockout at start
83
Safety circuit open /Burner flange open, extraneous light,
air pressure, POC - Alarm lockout at start
85
Safety circuit open /Burner flange, air pressure, fuel
pressure, POC - Alarm lockout at start
87
Safety circuit open /Burner flange, extraneous light, air
pressure, fuel pressure, POC - Alarm lockout at start
Error
code
Diagnostic code
Meaning of the REC 27.100A2 system
Recommended measures