Technical description of the burner
4.9
Test boiler
The burner/boiler combination does not pose any problems if the
boiler is EC approved and its combustion chamber dimensions
are similar to those indicated in the diagram (Fig. 3).
If the burner must be combined with a boiler that has not been EC
approved and/or its combustion chamber dimensions are clearly
smaller than those indicated in the diagram, consult the
manufacturer.
The firing rates were set in relation to special test boilers,
according to EN 676 regulations.
In Fig. 3 you can see the diameter and length of the test
combustion chamber.
Example:
Output 350 kW: diameter 50 cm - length 1.5 m.
4.9.1
Commercial boilers
The burner/boiler combination does not pose any problems if the
boiler is EC approved and its combustion chamber dimensions
are similar to those indicated in the diagram (Fig. 3).
If the burner must be combined with a commercial boiler that has
not been EC approved (CE mark) and/or its combustion chamber
dimensions are clearly smaller than those indicated in diagram
(Fig. 3), consult the manufacturers.
Fig. 3
Combu
sti
on chambe
r
m
D715
Содержание RS 28
Страница 2: ...Translation of the original instructions ...
Страница 40: ...20144599 38 GB Appendix Electrical panel layout K1 RS 28 SINGLE PHASE 20129156 DIAGRAM A ...
Страница 41: ...39 20144599 GB Appendix Electrical panel layout K1 RS 38 SINGLE PHASE 20129158 DIAGRAM A ...
Страница 42: ...20144599 40 GB Appendix Electrical panel layout K1 RS 38 RS 50 THREE PHASE 20126558 DIAGRAM A ...
Страница 43: ...41 20144599 GB Appendix Electrical panel layout RS 28 RS 38 SINGLE PHASE 20143439 DIAGRAM B ...
Страница 44: ...20144599 42 GB Appendix Electrical panel layout RS 38 RS 50 THREE PHASE DIAGRAM B 20143440 ...
Страница 45: ...43 20144599 GB Appendix Electrical panel layout 20143441 RS 28 RS 38 SINGLE PHASE DIAGRAM C ...
Страница 46: ...20144599 44 GB Appendix Electrical panel layout 20143442 RS 38 RS 50 THREE PHASE DIAGRAM C ...