9
20168262
GB
Technical description of the burner
4.5
Electrical data
Tab. D
4.6
Maximum dimensions
The maximum dimensions of the burner are given in Fig. 1.
Bear in mind that inspection of the combustion head requires the
burner to be opened and the rear part drawn back on the slide
bars.
The dimensions of the open burner are indicated by position I.
Tab. E
Model
RLS 120/E FGR FS1
Main electrical supply
3~ 400V - 50Hz +/-10%
Auxiliary circuit electrical supply
1N ~ 230V - 50Hz
Fan motor
rpm
V
Hz
W
A
2890
380/415
50
2200
4.5
Pump motor
rpm
V
Hz
W
A
2700
230
50
550
3.6
Ignition transformer
V1 - V2
I1 - I2
230 V - 2 x 5 kV
1.9 A - 35 mA
Max. Absorbed electric power
main electrical supply
–
light oil
–
gas
W
2550
2550
Max. Absorbed electric power
auxiliary circuit electrical supply
–
light oil
–
gas
W
500
1300
Protection level
IP 44
H
L
M
F
O
E
I
C
A
B
D
F 1
S
N
G
G1
Fig. 1
20169315
mm
A
B
C
D
E
F
F1
G
G1
H
I
L
M
N
O
S
RLS 120/E FGR 886 330 556 640 950
245
192
189 218
425
1482
239
143
284
2”
DN65
Содержание RLS 120/E FGR
Страница 2: ...Translation of the original instructions ...
Страница 50: ...20168262 48 GB Appendix Electrical panel layout 0 0 0 0 1 2 3 2 1 3 4 1 5 5 5 6 5 7 5 5 5 5 5 5 5 5 5 5 6 5 ...
Страница 51: ...49 20168262 GB Appendix Electrical panel layout 01 2 3 4506 7 891 01 ...
Страница 52: ...20168262 50 GB Appendix Electrical panel layout 0 1 2 2 2 0 ...
Страница 54: ...20168262 52 GB Appendix Electrical panel layout 0 0 0 12 3456 7 12 3456 7 ...
Страница 57: ...55 20168262 GB Appendix Electrical panel layout 0 0 1 2 3 4 5 667 8 667 2 9 63 8 63 63 3 5 ...