COMMISSIONING AND MAINTENANCE
22
FAN MODE
—
open the door
—
press
The time indication starts to blink.
—
work
—
select the current time
Each time the key is pressed, the values changes by 1. by keeping
the key pressed down, the value changes faster.
—
confirm using
The time indication stops blinking.
3.2 Putting into service
After having completed all the operations required to prepare
for first commissioning, do the following to activate the device:
ON
OFF
—
set the system main switch to “ON”
—
activate the device with the remote control
—
check its operation in the different modes
9
The compressor activates 3 minutes after unit activation.
9
Refer to the user booklet as for the use of the remote control.
Start-up in cooling mode with low temperatures
When the room temperature is lower than 16°C, the unit does
not start in cooling mode. In case you need to check the unit op-
eration in these conditions, you can use the emergency switch.
1 Emergency switch
1
To switch on:
—
keep the emergency switch pressed down with a pointy
object until a double acoustic signal is emitted
—
the air-conditioner starts in cooling mode with high ven-
tilation speed and active air deflector
To switch off:
—
press the emergency switch again
9
This operation must be carried out in specific conditions and
not for usual operation.
Checks during and after the first commissioning
After starting the device, check that:
—
the current consumed by the compressor is less than the
maximum permitted
—
the device is operating under the recommended operating
conditions
—
the unit is able to stop and start up again
9
Should any of the above-listed controls have problems: turn
the device off and call the Technical Service immediately.
9
Do not touch the device pipes to prevent potential burns.
9
Take anti-static precautions in case of weather conditions
where humidity is less than 40%.
9
Avoid using mobile phones.
3.3 Temporary shutdown
In order to shut down the unit for periods of brief absences:
—
only use the remote control to disable the unit
3.4 Stop for an extended period of time
If the device has not been used for an extended period of time,
carry out the following operations:
—
start the device in ventilation mode
—
select the maximum speed
—
let the device run for 6 hours
—
deactivate the device with the remote control