Calibration of the thermal relay
The thermal relay (Fig. 20) serves to avoid damage to the motor
due to an excessive absorption increase or if a phase is missing.
For calibration 2), refer to the table indicated in the electrical
layout (electrical wiring by the installer).
In case of 230V power supply, change the motor connection from
star to delta and replace the thermal relay with the one supplied
with the burner.
To reset, in case of an intervention of the thermal relay, press
button "RESET" 1).
The button “STOP” 3) opens the NC contact (95-96) and stops
the motor.
Insert a screwdriver in the window “TEST/TRIP” 4) and move it in
the arrow direction (to the right) to carry out the thermal relay test.
6.15
Motor rotation
As soon as the burner starts, place yourself in front of the cooling
fan of the fan motor and check that it turns anticlockwise
(Fig. 21).
If this is not the case:
put the switch of the burner to “0” (off) and wait until the
control box carries out the switching off phase.
Invert the phases on the three-phase motor power supply.
ATTENTION
The automatic reset can be dangerous.
This operation is not foreseen in the burner
operation.
1
2
3
MAN
AUT
O
STOP
NO
98
97
96
95
RESET
NC
4
TEST/TRIP
Fig. 20
D8685
DANGER
Disconnect the electrical supply from the burner
by means of the system main switch.
Fig. 21
20162749
Содержание P 300 P/G
Страница 2: ...Translation of the original instructions...
Страница 46: ...20170350 44 GB Appendix Electrical panel layout 0 1 2 0 3 4 1 1 1 1 1 5 6 6 6 7 6 8 6 6 6 6 6 6 6 6 6 6 7 6...
Страница 47: ...45 20170350 GB Appendix Electrical panel layout 0 0 0 1 2 3 4 0 50 0 6 6 7 8 9 7 7 7 A B B B...
Страница 48: ...20170350 46 GB Appendix Electrical panel layout 0 0 0 1 2 3 4 0 50 0 6 6 7 84 9 8 4 7 7 7 A B B B...
Страница 52: ...20170350 50 GB Appendix Electrical panel layout 0 1 1 0 0 2 2 2 2 3 45 6 6 3 45 7 8 6 7 8 9 9 8 1 8 4 4 2 0...
Страница 55: ......