54
NexPolar
Function
Parameter
Description
Value range Default value Set value
Min
Max
System configuration
100
Code used to set the type of system:
1. Heat pump with fixed water temperature (clean contacts)
2. Heat pump with set-up of the climate curve (clean contacts)
3. Heat pump with control panel control
4. Monoblock Comfort with Control Panel as Thermostat
5. N.A.
6. Monoblock RS485
7. N.A.
1
7
1. A2W
Type of user
interface
101
Code used to indicate if and how the User Panel control interface is used:
0. Control panel not used (Input Relay active)
1. Control panel installed
2. Control panel used as programmer
0
2
0. Not used
Control panel
software release
102
The code indicates the Control panel software release
-
-
-
Lock
Control panel
software version
103
The code indicates the Control panel software version
-
-
-
Lock
Output test
104
Code used to force the Output ON to carry out the test (max 10 minutes)
0. No test
1. Water pump
2. Alarm/Ambient temperature reached
3. External heat source /Defrost
4. Auxiliary heat source required for ACS/Dehumidification
5. Electric trace heater / Additional water pump
6. 3-way valve
7. Not used
8. Not used
0
8
0. No test
Reset pump run-
time
105
This code is use to reset the water pump working hours to zero
no
yes
no
External heat source/
defrosting
106
Code is used to select the output connected to PIN 4 on the terminal board
1. Auxiliary heat source required
2. Defrost output signal
1
2
1
Humidity limit
107
Code used to set the humidity threshold limit to enable the output for the
external de-humidifier system
20
100
50%
Auxiliary source
required for ACS or
humidity control
108
Code used to select the output connected to PIN 11 on the terminal board
1. Auxiliary source required for ACS when External Air Temperature <
temperature set with code 148
2. Humidity control
1
2
2
Frost Delta set point
109
Code used to set the frost set point delta used by the antifreeze system as
per algorithm
0°C
6°C
1°C
Compressor run-
time reset
110
Code used to reset the compressor working hours to zero
No
yes
No
Flow switch status
111
The code displays the status of the flow switch:
0. Water not flowing
1. Water flowing
-
-
-
Lock
Heating climate
curve number
112
Code used to select the number of the heating climate curve.
0. No pre-set climate curve (the installer has to draw up the Climate Curve)
1-12. For more information on the curves, read the specific section
0
12
0
Heating water set
point
113
Code used to set the fixed set point of the heating water
20°C
60°C
45°C
Heating temperature
reduction in eco
mode
114
Code used to set the temperature reduction value for the fixed set point of
the heating water when the unit is in ECO mode.
1°C
20°C
5°C
Cooling water set
point
115
Code used to set the fixed set point of the cooling water.
4°C
25°C
7°C
Cooling temperature
reduction in eco
mode
116
Code used to set the temperature reduction value for the fixed set point of
the cooling water when the unit is in ECO mode.
1°C
10°C
5°C
Cooling climate
curve number
117
Code used to select the number of the cooling climate curve.
0. No pre-set climate curve (the installer has to draw up the Climate Curve)
1-2. For further information on the climate curves consult the control panel
manuals.
0
2
0
Min outdoor air
temperature in
heating mode
118
Code used to select the minimum outdoor temperature of the heating
climate curve, which depends on the country where the system is installed. -20°C +10°C
-7°C
Table of functions and installer parameters