OVERVIEW
M
ULTI
S
ENTRY
The UPS units of the
Multi Sentry
10 – 12 – 15 – 20 kVA range (VFI-SS-111 type) have been designed using the latest
technology available today so as to guarantee users maximum performance. The use of the new control PCBs based on
multiprocessor architecture (DSP +
µ
P inside) together with high frequency IGBT technology offers excellent performance both
in the input stage (absorbed current harmonic distortion
≤
3%) and in output (output voltage distortion
≤
1%).
Thanks to these and many other features plus the easy-to-use design, the
Multi Sentry
represents a new reference standard in
the three-phase UPS sector.
Depending on user requirements, there are two different versions available:
MCT
The
Multi Sentry MCT version
stands out by its
compact size and new, modern design. These
features make it suitable for any environment.
MST
The
Multi Sentry MST version
, offers longer
autonomy than the
MCT
version, thanks to the
possibility to double the number of batteries inside the
cabinet.
10 kVA
12 kVA
15 kVA
20 kVA
Nominal power
10000 VA
9000 W
12000 VA
10800 W
15000 VA
13500 W
20000 VA
18000 W
Output power factor
0.9
0.9
0.9
0.9
Weight (with
batteries)
MCT
180 Kg
182 Kg
190 Kg
195 Kg
MST
305 Kg
310 Kg
315 Kg
320 Kg
W x D x H
MCT
320 x 840 x 930 mm
MST
440 x 850 x 1320 mm
Accessories
Battery cabinets – Communication boards – Remote mimic panel