15
GENERAL
GENERAL
9
R
KOMBISOLAR 3S
combination storage cylinders are de-
livered without pumps. Suitably rated pumps must be pro-
vided and installed separately. Flow rate from the solar col-
lector circuit depends on the type and number of collectors
installed. For further information, consult the manual for
the collectors.
9
The domestic hot water system MUST INCLUDE an expansion
vessel, safety valve, automatic vent valve and combination
storage cylinder drain cock.
9
Safety valves must be connected to a suitable collection and
drain system. The manufacturer declines all responsibility
for damage caused by water escaping from the safety valve.
9
The selection and the installation of the components of the
system is the responsibility of the installer, who must op-
erate in accordance with good practice and current Legis-
lation.
9
Circuits filled with anti-freeze must be fitted with water dis-
connectors.
8
LOCATION OF SENSORS
R
KOMBISOLAR 3S
combination storage cylinders incorporate
sockets for solar controller and boiler sensors. Make sure that
these sensors are pushed firmly home into the sockets.
9
The installer is responsible for making all necessary con-
nections to the boiler and solar collectors. Installers must
use their expertise to ensure proper installation and func-
tioning in compliance with all applicable legislation.
Mod. 430-550
SC
SC
T
S
SRS
T
Temperature gauge socket (10 mm)
S
Temperature sensor socket (16 mm)
SC
Boiler temperature sensor socket (16 mm)
SRS
Solar controller temperature sensor socket (16 mm)
Mod. 750-1000
SC
SC
T
S
SRS
T
Temperature gauge socket (1/2")
S
Temperature sensor socket (8 mm)
SC
Boiler temperature sensor socket (16 mm)
SRS
Solar controller temperature sensor socket (16 mm)
9
In case of a probe, any electric junction between probe ca-
ble and extensions for the connection to the electric panel
must be soldered and protected with a sheath or a suitable
electric insulation.