BURNER STARTING DIFFICULTIES AND THEIR CAUSES

The symbol, visible on the reading disc of the pointer, shows the kind of problem.

 The control box does not start at the thermostats closing, because of:

-  lack of gas;
-  the gas pressure switch does not close the contact: bad set;
-  the air pressure switch changed over in operation position; 
- the control box fuse is broken;
-  the servomotor does not totally change over the closing circuit in being between the terminals 11 and 8 of the

control box.

 Stop at the start-up, because of:

-  the servomotor does not change over the max. opening circuit in being between the terminals 9 and 8 of the

control box.

P Lock-out

The air pressure switch does not change over, because of:
-  defective contact;
-  insufficient pressure of the air.

 Lock-out

Unperfect operation of the flame detecting circuit, because of:
-  probe to earth;
-  defective internal amplifier.

 Stop during pre-purge phase, because of:

The servomotor does not change over the minimal opening circuit in being between the terminals 10 and 8 of the
control box.

1 Lock-out due to flame signal lack; if:

-  the ionisation probe is not inside of the flame;
-  the probe connection to the control box is disconnected;
-  the ionization current is insufficient (min. 6 µA).

 Lock-out during operation due to:

-  flame signal lack;
-  no air pressure.

NOTICE

-  If lock-out occurs between the start-up and the pre-ignition phase without that a symbol comes out, the cause is

the flame simulation.

-  If the burner repeats continuously the start-up cycle without lock-out occurring, this is due to the “oscillation” of

the  gas  pressure  switch  caused  by  a  setting  very  near  to  the  gas  network  pressure,  therefore  the  pressure
decreasing at the burner start-up is sufficient to actuate the gas pressure switch causing a new start-up.

Содержание GAS 5 P/M

Страница 1: ...Installation use and maintenance instructions 2915246 2 07 2016 Forced draught gas burner Progressive two stage or modulating operation CODE MODEL TYPE 3753581 GAS 5 P M 535 T80 GB...

Страница 2: ...M These products are in compliance with the following Technical Standards EN 676 EN 12100 and according to the European Directives MD 2006 42 EC Machine Directive LVD 2014 35 UE Low Voltage Directive...

Страница 3: ...ration two stages progressive modulating kit with controller available upon request Fuel natural gas Pci 8 10 kWh m3 7000 8600 kcal m3 Minimum gas pressure for maximum output 9 8 mbar are needed measu...

Страница 4: ...NS COMBUSTION CHAMBER PRESSURE MAXIMUM OUTPUT Min output 155 kW 133 300 kcal h Boiler front plate drilling Length available with special blast tube to be separately required Burner 160 160 165 M12 D17...

Страница 5: ...ain 550 kW it is necessary a gas pressure of 9 mbar and the combustion head set as indicated at page 8 If the combustion chamber is pressurized at 2 mbar the pressure detected at the testpoint 9 is 9...

Страница 6: ...Loosen the screws 2 unhook the tension rod of the air damper 1 remove the connecting lead of the servomotor withdraw the group A from the group B After the setting re assemble and verify that the ten...

Страница 7: ...out y the factory Key to layout CMV Motor contactor LFL Control box MB Burner terminal strip MV Fan motor PA Air pressure switch RT Thermal cut out SM Servomotor SO Ionisation probe SP Plug socket TA...

Страница 8: ...urner must be stopped every 24 hours of operation by means of an hours counter to be connected in series with the adjustment devices Key to layout BP Pressure probe BT Temperature probe MB Burner term...

Страница 9: ...ontroller modulating version 8 Pre sheared holeg Further prospective signals or controls can be connected to the burner wiring terminal board by removing the metal weld nuts from the pre sheared holes...

Страница 10: ...justment pressure by turning slowly clockwise the knob till reaching the burner lock out Thereafter turn the knob anticlockwise for 1 mbar and repeat the burner start up for checking the regularity if...

Страница 11: ...he plate 4 Tighten the screws 1 Gas setting Loosen the screw 5 move the ring 6 so that the pointer 7 is coincident with the desired setpoint 8 Tighten the screw 5 Attention the set point number is the...

Страница 12: ...controls the min stroke and remains al ways positioned on 0 in this way when the burner is off the air damper is totally closed Orange cam it controls the minimal modulating power It is set by the fa...

Страница 13: ...file 7 of the cam by gradually acting on the screws 9 MINIMAL OUTPUT SETTING Gas Disjoint the cam with adjustable profile 6 by means of the button 5 Turn manually anticlockwise the cam till to reach t...

Страница 14: ...ange 25 50 the change from 90 to 60 of the tension rod will be sufficient Should this ratio be in higher range 50 100 in this case further to position the tension rod on 60 it shall be shortened Proce...

Страница 15: ...TION CURRENT The minimum current necessary for the control box operation is 6 A The burner normally supplies a higher current value so that no check is needed However if a measurement of the ionizatio...

Страница 16: ...operation of the flame detecting circuit because of probe to earth defective internal amplifier Stop during pre purge phase because of The servomotor does not change over the minimal opening circuit i...

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www riello com...

Отзывы: