TURN TO THE RIGHT:  (sign 

+

)

In order to increase the volume of air entering the com-
bustion chamber and thus diminishing its pressure.
There is a reduction of CO

2

 and the adhesion of the

flame to the air diffuser disc improves. 

(Setting advisable for ignitions at low temperatures).

TURN TO THE LEFT:  (sign 

)

In order to reduce the volume of air entering the com-
bustion chamber and thus increasing its pressure. The
CO

2

 improves and the adhesion of the flame to the dif-

fuser tends to reduce. 

(This setting is not advisable for ignitions at low temper-
atures).

In any case do not bring the combustion head setting
more than one point away from that indicated in the
schedule. One set-point corresponds to 3 turns of the
rod; a hole 

(3)

 at its end facilitates counting the number

of turns.

 

AIR DAMPER ADJUSTMENT

, (fig. 4)

   

The regulation of the air-rate is made by adjusting the
air damper 

(1)

, after loosing the screws 

(2)

When the optimal regulation is reached, 

screw tight

the screws (2).

 

The settings indicated in the schedule are purely

indicative. 
Each installation however, has its own unpredictable
working conditions: actual nozzle output; positive or
negative pressure in the combustion-chamber, the
need of excess air, etc. All these conditions may
require a different air-damper setting.

It is important to take account of the fact that the air
output of the fan differs according to whether the
burner has its metal cover fitted or not.  

Therefore we recommended to proceed as follows:
–  adjust the air damper as indicated in the schedule at

page 5;

–  mount the cover, simply by means of the upper

screw;

– check smoke number;
–  should it become necessary to modify the air output,

remove the cover by loosening the screw, adjust the
air damper, remount the cover and finally recheck the
smoke number.

NOTE:

When the burner works at a firing rate higher
than 9 kg/h remove the panel fitted inside the
metal cover, (see figure 5).

1

2

3

6

D5671

Fig. 3

PANEL

D7178

Fig. 4

Fig. 5

1

2

D5231

4

Содержание G10 LC

Страница 1: ...20013654 2 05 2009 Installation use and maintenance instructions Light oil burner CODE MODEL TYPE 20013617 G10 LC 464T1 GB CN One stage operation...

Страница 2: ...safety start up use and maintenance of the burner DELIVERY OF THE SYSTEM AND THE INSTRUCTION MAN UAL When the system is delivered it is important that The instruction manual is supplied to the user b...

Страница 3: ...ly Single phase 230V 10 50Hz Motor Run current 0 8A 2850 rpm 298 rad s Capacitor 4 F Ignition transformer Secondary 8 kV 16 mA Pump Pressure 7 15 bar Absorbed electrical power 0 170 kW 1 Return line 2...

Страница 4: ...9 83 83 170 4 5 105 It is necessary that the insulating gasket 9 fig 1 is placed between the boiler door and the burner flange This insulating gasket has six holes which if necessary can be modified a...

Страница 5: ...valve PRIMING THE PUMP Start the burner and wait for the priming Should lock out occur prior to the arrival of the fuel await at least 20 seconds before repeating the operation A filter must be instal...

Страница 6: ...neath the ignition transformer on a plug in support TESTING Check the shut down of the burner by opening the thermostats ATTENTION Do not connect burner s grounding to failure indicator terminal This...

Страница 7: ...n fitting the nozzle with the blast tube removed It depends on the output of the burner and is carried out by rotating the reg ulating rod till the terminal plane of the blast tube is level with the s...

Страница 8: ...per 1 after loosing the screws 2 When the optimal regulation is reached screw tight the screws 2 The settings indicated in the schedule are purely indicative Each installation however has its own unpr...

Страница 9: ...ion head one set point further ahead than indicated in the instructions Example the instructions require to set the combustion head on set point 3 Instead the setting is made on set point 4 4 FAN AIR...

Страница 10: ...20013654 CN Technical Assistance Centre Assistance Centre Maintenance Contract...

Страница 11: ...C 2004 108 EC 73 23 EEC 2006 95 EC 98 37 EEC 92 42 EEC O IP 40 EN 60529 464T1 54 120 kW 4 5 10 kg h 20 C 4 6 mm2 s 230V 10 50Hz 0 8A 2850 rpm 298 rad s 4 F 8 kV 16 mA 7 15 bar 0 170 kW 1 2 3 4 5 6 7 8...

Страница 12: ...20013654 2 CN EN 267 0 8 0 0 4 4 5 6 kg h 50 60 120 kW D5669 70 80 90 100 110 0 2 0 6 mbar 7 8 9 10 305 108 261 140 40 4 5 262 1 1 204 D5670 189 83 83 170 4 5 105 9 1 6 D5242 2 2 D5572 S7385...

Страница 13: ...Hg 20 H m L m I D 8 mm I D 10 mm 0 5 1 1 5 2 10 20 40 60 20 40 80 100 A A H m L m I D 8 mm I D 10 mm 0 0 5 1 1 5 2 3 3 5 35 30 25 20 15 8 6 100 100 100 90 70 30 20 H max 4 m H H max 4 m min 0 1 m D521...

Страница 14: ...20013654 4 CN 50V T6A N L M S7026 1 mm2 A 230V 50Hz N L 230V 0 5A max 1 2 3 4 5 6 7 8 9 530SE T T 1 N 2 L 3 A 3 2 1 D5228...

Страница 15: ...B Steinen S Q Danfoss S 12 bar 12 bar 14 bar 12 bar 1 50 GPH 3 6 mm 2 1 3 P 6 GPH bar kg h 4 1 10 60 12 4 4 2 3 1 25 60 12 5 0 2 5 3 4 1 50 60 12 6 0 3 3 8 1 75 60 12 7 0 4 4 2 00 60 12 8 0 5 5 2 25...

Страница 16: ...20013654 6 CN CO2 CO2 1 3 3 4 2 1 2 5 9kg h D7178 1 2 D5231 1 2 3 6 D5671 3 4 5 4...

Страница 17: ...7 20013654 CN 6 5 C 1 6 2 12 bar 5 C 14 bar 3 3 4 4 1 A 4 0 3 mm D5288 A 4 5 0 5 mm 6 12s D5229 12s 5s...

Страница 18: ......

Страница 19: ......

Страница 20: ...I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www rielloburners com Manufacturing site Riello Heating Equipment Shanghai CO LTD No 388 Jinbai Road Jinshan Industrial Zone 201506 Shang...

Отзывы: