ELECTRICAL WIRING
Brown
Wh
it
e (5
0V)
Blue
Motor
Capacitor
Regulating thermostat
Ne
ut
ral
Switch with fuse
6A
max.
N
L
M
~
S7026
Black
NOTES
– Wires of 1 mm
2
section.
– The electrical wiring carried out by the installer
must be in compliance with the rules in force in
the Country.
– To remove the control-box from the burner,
loosen screw (A)
(see figure)
and pull towards
the arrow.
– The photoresistance is fitted directly into the con-
trol-box
(underneath the ignition-transformer)
on
a plug-in support.
TESTING
Check the shut-down of the burner by opening the
thermostats.
ATTENTION
Do not connect burner’s grounding, to failure
indicator terminal
. This may result the destroy
of the control box.
WARNING
Do not exchange the neutral with the phase.
230V
~
50Hz
N
L
Limit thermostat
with manual resetting
Remote lock-out lamp
(230V - 0.5A max.), if required
1
2
3
4
5
6
7
8
9
Blue
Brown
Terminal block of
control-box
530SE
*
Valve
T
T
RUN OF THE ELECTRICAL CABLE
1
- Grommet
N
- Neutral
2
- Cable-clamp
L
- Phase
3
- Terminal block
- Burner-earth
A
3
2
1
D5228
Black
CA
RRIED-OUT B
Y
THE
INSTALLER
CA
RRIED-OUT IN THE
FA
CTOR
Y
Содержание G10 LC
Страница 10: ...20013654 CN Technical Assistance Centre Assistance Centre Maintenance Contract...
Страница 16: ...20013654 6 CN CO2 CO2 1 3 3 4 2 1 2 5 9kg h D7178 1 2 D5231 1 2 3 6 D5671 3 4 5 4...
Страница 17: ...7 20013654 CN 6 5 C 1 6 2 12 bar 5 C 14 bar 3 3 4 4 1 A 4 0 3 mm D5288 A 4 5 0 5 mm 6 12s D5229 12s 5s...