Installation

5.14 Programming menu

5.14.1 General notes

The programming menu can be accessed via the integrated reset
button, or by remote reset during OPERATION and in STAND-
BY.
If in page menu the reset or remote reset button is not pressed
within 10 seconds the page will be automatically be exited and
there will be a green LED blinking for the time set.

If the number of presses on the reset or remote reset button ex-
ceeds the maximum allowable, the value that stays in memory
will be the maximum one.
If the reset or remote reset button is pressed for more than 60
seconds, a button error will be displayed and the control box will
restart.

5.14.2 Block diagram for entering the menu

Tab. L

POST-PURGING/

CONTINUOUS 

PURGING

10 SEC.

INTERMITTENT 

OPERATION

20 SEC.

SWITCHING OFF 

TEST

5 SEC.

LONG PRE-PURG-

ING

30 SEC.

DISPLAYING 

LOCKOUT

LOGS

35 SEC.

PROGRAMMING 
MENU PARAME-

TER RESET

40 SEC.

2 RED

AUTOMATIC

EXIT

1 GREEN

10 SEC. AFTER

RELEASE

3 GREEN

5 GREEN

6 GREEN

7 GREEN

OPERATION (WITH FLAME) AND STAND-BY

TYPE OF 
FUNCTION

NUMBER 

EXIT

BLINKS

RELEASE 
TIME
BUTTON

BURNER STATE

S9653

 Fig. 22

10 SEC. AFTER

RELEASE

10 SEC. AFTER

RELEASE

10 SEC. AFTER

RELEASE

10 SEC. AFTER

RELEASE

Function

Button 
release time

No. of blinks of 
the led per
menu page

No. of pressings
of the reset button

No. of blinks of 
the LED (green)

Quitting the menu

Switching off

test

5s 

 t < 10s 

2 blinks 

RED

/ none

/ none

Automatic, at the

end of the blink

Post-purging/

Continuous 

purging

10s 

 t < 15s

1 GREEN blink

1 = 1 minute

2 = 2 minutes

3 = 3 minutes

4 = 4 minutes

5 = 5 minutes

6 = 6 minutes

7 = continuous purging

8 = 0 m (deactivated) 

(

default

)

1 blink

2 blinks

3 blinks

4 blinks

5 blinks

6 blinks

7 blinks

8 blinks

10 sec. after the release of the

button

Intermittent

operation

20s 

 t < 25s

3 blinks

GREEN

1 = 1 hour

2 = 24 hours (

default

)

1 blink

2 blinks

10 sec. after the release of the 

button

Pre-purging

long

30s 

 t < 35s

5 blinks

GREEN

1 = activated

2 = deactivated

      (

default

)

1 blink

2 blinks

10 sec. after the release of the 

button

Display

lockout logs

35s 

 t < 40s

6 blinks

GREEN

1 = last lockout

2 = 9th lockout

3 = 8th lockout

4 = 7th lockout

5 = 6th lockout

6 = 5th lockout

7 = 4th lockout

8 = 3rd lockout

9 = 2nd lockout

10 = less recent lockout

Displaying the 

type of lockout

according to 

Tab. I

10 sec after the release of the 

button (if at level 1).

When at level 2, 10 sec after the 

display of the type of lockout or 

else pressing the button again 

before 10 sec you return to level 

1 from where, 10 seconds after 

nothing has been done to the 

buttons, you exit the menu

Parameter 

reset 

programming 

menu

40s 

 t < 45s

7 blinks

GREEN

1 = reset of the

      lockout logs

2 = reset of the no. of

      lockouts

3 = reset of hours of 

      operation

4 = reset of the no. of

      heat requests

5 = restoration of

      default values of the 

      menu parameters

/

10 sec. after the release of the 

button

Содержание 3755119

Страница 1: ...Installation use and maintenance instructions 20146119 2 06 2018 Forced draught gas burner One stage operation CODE MODEL TYPE 3755119 RIELLO 40 GS3 551T1 GB...

Страница 2: ...Translation of the original instructions...

Страница 3: ...ry checks 14 5 4 1 Control of the supply 14 5 4 2 Control of burner characteristics 14 5 5 Operating position 14 5 6 Securing the burner to the boiler 15 5 7 Combustion head adjustment 15 5 8 Position...

Страница 4: ...enu 28 5 14 3 Shut down test 29 5 14 4 Post purging and continuous purging 29 5 14 5 Intermittent operation 29 5 14 6 Setting the long pre purging 29 5 14 7 Displaying the lockout log 30 5 14 8 Resett...

Страница 5: ...gnago VR Italy Tel 39 0442630111 www rielloburners com Distributed by RIELLO NV Ninovesteenweg 198 9320 Erembodegem Tel 053 769 030 Fax 053 789 440 e mail info riello be URL www riello be This documen...

Страница 6: ...ed out correctly may cause damage to the ma chine and or injury to people DANGER DANGER LIVE COMPONENTS This symbol indicates operations which if not car ried out correctly lead to electric shocks wit...

Страница 7: ...vent of damage to things or injury to people if such damage injury was due to any of the following causes incorrect installation start up use and maintenance of the burner improper incorrect or unreas...

Страница 8: ...intenance Only those parts envisaged by the manufacturer can be replaced 3 2 Personnel training The user is the person body or company that has acquired the machine and intends to use it for the speci...

Страница 9: ...ze Fuel Natural gas Gas oil LPG Variations Electrical supply of the system 1 230 50 1 230 60 G S 3 1 230 50 BASIC DESIGNATION EXTENDED DESIGNATION 1 230V 50Hz 1 230V 60Hz Light oil Natural gas K Conic...

Страница 10: ...on pipe coupling Rp 1 2 R 3 8 Model RIELLO 40 GS3 Type 551T1 Heat output Hi 1 min max kW kcal h 11 35 9 500 30 000 Fuel Family 2 NCV 8 12 kWh m3 7 000 10 340 kcal m3 Pressure min 10 mbar max 200 mbar...

Страница 11: ...t the manufacturers 4 7 Correlation between gas pressure and burner output To obtain the maximum output Fig 3 it is necessary to have 4 5 mbar measured on the pipe coupling with the combustion cham be...

Страница 12: ...e 13 Pressure test point 14 Combustion head 15 Electrode probe 16 Gas train elbow 4 9 Burner equipment Screws with nuts No 4 Insulating gasket No 1 Cover fixing screw No 1 Cable grommet No 1 Reducing...

Страница 13: ...e the control box from the burner it is necessary to Fig 5 disconnect all the connectors connected to it all the plugs the high voltage cables and the earth wire TB unscrew the screw A and pull the co...

Страница 14: ...ollisions can negatively affect the safety func tions In this case the servomotor must not be operated even if it displays no evident damage Assembly notes The actuator is mounted on the burner air se...

Страница 15: ...r If the smoke pipe is closed the burner must be drawn back till the extraction of blast tube from the furnace Before oper ating in this way take the voltage off 5 3 Handling The transport weight is g...

Страница 16: ...must not be abandoned as they are potential sources of danger and pollution they should be collected and disposed of in the appro priate places WARNING A burner label that has been tampered with re m...

Страница 17: ...rews A Fig 10 without removing them pull back the head rotating it by about 180 extract the head tilting it downwards Example The burner is installed in a 21 kW boiler Considering an efficiency of 90...

Страница 18: ...far as the required point 2 Once optimum adjustment has been reached fix the screws 3 and 5 The adjustment of the damper varies in each single application so it is necessary to use a calibration tool...

Страница 19: ...provided separately from the burner Supplied separately for its adjustment see the enclosed instructions The train burner combination is indicated in Tab E Tab E Explosion danger due to fuel leaks in...

Страница 20: ...Connect the 6 pin plug 2 Fig 15 of the gas train to the 6 pole socket 9 Fig 4 on pag 10 of the burner DANGER Disconnect the electrical power using the main switch Check that there are no gas leaks Pa...

Страница 21: ...cle arrest must be ensured within 24 hours with the use of a time switch positioned in series with the thermostatic line Refer to the wiring diagrams The electrical safety of the device is obtained on...

Страница 22: ...t invert the neutral with the phase in the electrical supply line Check that the electrical supply of the burner corresponds to that shown on the identifica tion label and in this manual The section o...

Страница 23: ...e ts Safety time tsm Standby time for servomotor opening of the electric damper opener V1 Gas valve Normal operation t2 t1 t3 t4i ts HT FM ID V1 LED P M LED t4l PG P M SM SO SO tsm 20147598 POWER SUPP...

Страница 24: ...ge over within t3a there is a lockout max 15 t3r A recycle attempt is made if there is an air pressure drop during the pre purging stage there is then a lockout in the event of a second loss of air pr...

Страница 25: ...link 0 5 0 5 Lockout for maximum number of cycle repetitions flame loss during operation RED Fast blinking 0 2 0 2 Lockout due to loss of air pressure or after repetition of the pre purging that occur...

Страница 26: ...s the flame goes out and the start up sequence restarts If the switch off test is enabled the number of repetitions of the start up sequence see paragraph Recycle and limit of repeti tions on page 24...

Страница 27: ...er stops interrupts the operating cycle and remains in stand by sig nalling a fault The fault is indicated by way of the blinking LED see paragraph Fault diagnostics lockouts on page 23 The burner res...

Страница 28: ...ff in the absence of the heat request for a pre set time The burner switches off the flame when the heat request thermo stat opens and the fuel supply to the gas valve stops The post purging function...

Страница 29: ...op erating hours Together with the operating hours also the number of the burner s 1st stage valve openings is saved In the menu see paragraph Programming menu on page 28 it is possible to independen...

Страница 30: ...tton No of blinks of the LED green Quitting the menu Switching off test 5s t 10s 2 blinks RED none none Automatic at the end of the blink Post purging Continuous purging 10s t 15s 1 GREEN blink 1 1 mi...

Страница 31: ...post purging function the exit menu occurs without saving the setting value If heat request stops during the LED blinking occur exit menu but the setting value is stored 5 14 5 Intermittent operation...

Страница 32: ...number of lockouts the operating hours the number of ignitions and recov er the menu s default see paragraph Block diagram for enter ing the menu on page 28 Sequence for setting and restoring the para...

Страница 33: ...t due to air pressure switch not closing after a heat request or af ter a recycle due to flame loss during operation After 15 seconds the air pressure is too low the head has been poorly adjusted The...

Страница 34: ...the knob anticlockwise to an extent that is around 20 of the adjusted value and then check that the burner starts up properly If the burner locks out again turn the knob slightly in an anticlock wise...

Страница 35: ...uction areas and in the combustion product waste pipe Carry out an analysis of the combustion flue gases Significant differences with respect to the previous measure ments indicate the points where mo...

Страница 36: ...tion on page 14 For accessing to the interior of the burner loosen the screws that secure the cover and proceed with the maintenance operation Check the operation Start up of the burner with a sequenc...

Страница 37: ...ng position and there are not short circuits The gas pressure switch does not close its contact Adjust them The connections in the control box are wrongly inserted Check and connect completely all the...

Страница 38: ...mmedi ately and the motor stops The pressure then starts to increase again the pressure switch closes the start up cycle be gins again and so on Lower and set the pressure switch Faults Possible Cause...

Страница 39: ...pendix Accessories Burner Standard length mm Long head length mm Code RIELLO 40 GS3 100 125 3000820 Burner Code RIELLO 40 GS3 3000881 Burner Code RIELLO 40 GS3 3000888 Burner Code RIELLO 40 GS3 300275...

Страница 40: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www riello com...

Отзывы: