10
INSTALLATION
INSTALLATION
Proceed as follows to remove the storage cylinder from the pallet:
− Place a platform of about half the height of the pallet near
the storage cylinder. Make sure the platform is able to sup-
port the weight of the storage cylinder.
− Remove the pallet fastening brackets
− Carefully rotate and slide the storage cylinder until it rests
on the platform
− Make sure that the storage cylinder is perfectly stable, and
then remove the pallet
− Carefully rotate and slide the storage cylinder off the plat-
form on to the floor
− Remove the platform. Position the storage cylinder as re-
quired.
Adjust the feet to ensure that the storage cylinder is perfectly level.
17
9
PLACE OF INSTALLATION
R
RBS 1S
storage cylinders can be installed in any room where
there is no specific requirement for an electrical protection rating
higher than IP X0D.
X
X
X
Y
Z
DESCRIPTION
RBS 1S
X
≥ 300
mm
≥ 11 13/16
inch
Y
≥ 600
mm
≥ 23 5/8
inch
Z
≥ 700
mm
≥ 27 9/16
inch
NOTE:
the above-indicated dimensions are recommended for a
correct maintenance and access to the device.
9.1
Installation in older systems and systems
requiring modifications
When the
R
RBS 1S
appliance is installed on old systems or ones
that need modernising, make sure that:
− Make sure that the system is fitted with safety and con-
trol devices in accordance with applicable legislation and
standards
− Make sure that the central heating circuit has been flushed
out to remove all sludge and lime scale, and has been
vented and seal tested
− There is a treatment system used when the delivery/supply
water is considered special (reference values can be taken
from the table in the section “Water quality requirements“).