17
INStALLAtION
Positioning on floor
1
Fastening screw M4
2
Anti-vibration element (supplied)
3
Spirit level
1
2
3
—
screw the unit to the ground
—
tighten using a torque wrench
—
apply a tightening torque of 3.5 Nm
Provide for lifting of the unit from the floor:
—
20 mm without conveying of the condensate outlet
—
90 - 100 mm to allow for the condensate discharge
9
If the device is installed in an area that is subject to heavy
snowfalls, place the unit in a raised position so as to pre-
vent the air flow from being blocked or install a roofing to
protect it.
9
Adequate anti-freeze systems should be used for installa-
tions in extremely cold areas, where there is a possibility of
freezing.
9
While operating in heating mode, the unit generates con-
densate, which will deposit on the support surface if there is
not discharge. This could freeze if the outdoor temperatures
are below zero, thus creating a hazard. In this case, appro-
priate barriers should be installed in order to prevent people
from approaching the unit.
1
Lifting from the top
2
Condensate discharge connector
1
2
Model
25
35
50
Refrigeration characteristics
Condensate discharge
attachment Ø
mm
16
Hanging position
9
Properly sized supporting brackets must be used if the devi-
ce is installed in suspension.
9
Ensure that the wall section does not include bearing ele-
ments, pipes or electric lines.
1
Supporting brackets
2
Anti-vibration element (supplied)
3
Fastening screw M4
1
2
3
2.9
Installation on old systems or systems in need
of upgrading
When
R
AARIA MONO PLUS
is installed on old systems or sy-
stems in need of upgrading, it is recommended to ensure that:
—
the electrical system is compliant with the applicable re-
gulations and has been installed by qualified professionals
9
In the event of a replacement, the system must be inspected
by the designer or by another competent person, and must
be compliant with the technical requirements, as well as
the current legislations and regulations.
9
The manufacturer shall bear no responsibility for any dama-
ges caused by incorrect system installation.
2.10
Refrigerating connection
The dimensions and positions of
R
AARIA MONO PLUS
cooling
connections are shown hereunder.