30
COMMISSIONING AND MAINtENANCE
Led 1 Description
Remarks
17
4-way valve
malfunction
The alarm activates 5 minutes
after the unit start
The alarm activates when, in
Heating mode, the temperature
detected by the indoor unit heat
exchanger probe is less than or
equal to 15°C for 1 minute and for
3 times in an hour
18
Deviate from the
normal for the
compressor
The unit resets after problem
resolution
19
Power module
malfunction
After 3 consecutive interventions
in 10 minutes, the unit resets
after problem resolution
20
Electronic board
overtemperature
protection sensor
fault
After 3 consecutive interventions
in 1 hour, the unit resets after
problem resolution
21
Internal unit
overload
The unit resets after problem
resolution
22
Internal unit anti-
freeze protection
The alarm activates when the
indoor unit heat exchanger
probe is lower than the setpoint
for 2 minutes
The unit resets after problem
resolution
24
Compressor motor
overcurrent
The unit resets automatically
25
Overcurrent
protection for
single- phase of the
compressor
The unit resets after problem
resolution
In the presence of operating abnormalities, the unit is secured
and blocked.
9
Safety block can occur randomly.
9
Wait for at least 10 minutes before restarting the unit.
9
If the fault occurs again, an accurate check of the device
components is required. Contact
R
Technical Support
Service.
9
Indoor units with display signal faults with an alphanumeric
code. Consult the matching outdoor unit instruction booklet
for the installer.