16
INStALLAtION
9
Do not tilt the equipment over 15°
9
The unit’s weight is concentrated on the compressors side
(connection covering side).
0
The packing material must not be disposed of in the sur-
rounding environment and must be kept out of children
reach, as it can be dangerous. It must be disposed of accor-
ding to the regulations in force.
2.6
Place of installation
The location of
R
AARIA MONO PLUS
devices must be determi-
ned by the system's designer or by another competent person,
and must take into account the technical requirements, as well
as any current local regulations that require specific permits to
be obtained. (e.g.: zoning, architectural, environmental pro-
tection, etc.).
It is therefore recommended to obtain all the necessary permits
before installing the device.
R
AARIA MONO PLUS
is designed for outdoor installation.
Avoid:
—
positioning the unit in air shafts and/or basement window
wells
—
any obstacles or barriers that will cause the expelled air to
recirculate
—
locations with aggressive or explosive atmospheres or with
inflammable fluids
—
confined locations in which the device's sound levels mi-
ght be compounded by reverberations or resonances
—
proximity to bedrooms and rooms for resting
—
positioning in corners where dust, leaves, or any other
materials typically accumulate, which could compromise
the device efficiency by obstructing the airflow
—
situations in which the air expelled from the device might
enter the habitation through doors or windows, thus cre-
ating an inconvenience for the people inside
—
situations in which the air expelled from the device will
encounter resistance from opposing winds
—
direct exposure to sunlight and proximity to heat sources
9
Avoid placing the unit less than 1 metre away from radio and
video systems.
9
If the unit is installed in a windy location, fit an anti-wind
grille to protect the fan and check the correct functioning of
the unit.
9
Decide where to place the unit considering the length of co-
oling lines and the maximum difference of height allowed
between the devices.
2.7
Recommended distances
The distances for the device installation and maintenance are
shown in the figure. The indicated spaces are necessary in order
to prevent the airflow from being blocked, as well as to allow
normal cleaning and maintenance operations to be carried out.
300
500
30
0
60
0
500
2.8
Positioning
R
AARIA MONO PLUS
devices must:
—
be positioned on a level surface that is capable of suppor-
ting their weight
—
be positioned on a sufficiently rigid surface that will not
transmit any vibrations to the underlying or adjacent ro-
oms
9
Use the anti-vibration supports supplied with the device.
A
B
C
D
Model
25
35
50
foot print dimensions
A
mm
130
130
115
b
mm
510
510
590
C
mm
160
160
115
D
mm
313
313
324
They can be placed on the floor or suspended on supporting