63
COMMISSIONING AND MAINTENANCE
ELECTRODE POSITIONING
The positioning of the ignition electrodes (A) is fundamental to
obtain reliable flame ignitions.
Check their state of wear and correct positioning, as shown in
the figure, and replace them if necessary.
±0.5
5
±0.5
63
A
9
It is essential to respect the dimensions in the figure.
REMOVING THE ELECTRODES
Proceed as follows to remove the electrodes:
− Loosen the screw (1)
− Extract the electrodes and check them for wear
Reverse the above steps to reassemble.
1
REMOVING THE BURNER CONTROLLER
The burner cover has to be removed first in order to remove the
controller.
Proceed as follows:
− Loosen the screw (1), open the cover (2) and remove all
the components inside
− Remove the coil (3)
− Unscrew and remove the two screws (4).
2
1
3
4
4
9
This operation must be performed with the burner turned
off and mains power disconnected.
CLEANING THE FAN
9
Clean the inside and the rotor blades of the fan unit to remove
any build-up of dust. Accumulated dust reduces the air flow and
therefore reduces combustion efficiency, leading to increased
emissions.
9
Perform maintenance operations paying attention not to dam-
age or unbalance the fan during cleaning operations.
Proceed as follows
− remove the socket (1), the cable from the cable clamp (2), undo
the screws (3) and take out the air damper unit (4);
− clean the fan and the inside of the suction inlet, using a suit-
able brush and compressed air.;
− if necessary, gently remove the fan by undoing the screw (5).
1
2
3
4
5
9
When reassembling the fan, it is important to put it back in
the correct position (B) and tighten the screw (5).
B
51 ± 0.2 mm
5
Ventilatore
− Reverse the above steps to reassemble. Take care to re-
place all burner parts in their original positions.