COMMISSIONING AND MAINTENANCE
4.4
Error List
When a technical anomaly occurs, the control interface display
shows a text message (small digit) and a number (large digit),
which indicate the type and level of the detected error.
There are 3 error levels:
1
Permanent: heating and/or DHW requests are suspended
and burner and circulator are switched off. For the error to
disappear, keep the key ENTER/RESET on the control inter-
face pressed for 3 seconds or reset the power supply by
using the main switch.
2 Temporary: heating and/or DHW requests are suspend-
ed and burner and circulator are switched off. The error
disappears automatically when the cause which generated
it is solved.
3 Alert: the thermal unit is not locked out, but its functions
may be limited according to the signalled alert code.
The log of the last ten errors occurred can be viewed through
the error log (menu 9000 - installer level) (from Par. 9001 to Par.
9010).
4.4.1
Permanent Errors
Message
Error No.
Description
Loc
10
Failed ignition/Burner error (see
page **cross reference non trova-
ta** code of colours to identify the
error).
Loc
20
Intervention of safety thermostat or
flue limit thermostat
Loc
40
Insufficient pressure primary circuit
Loc
42
Pressure transducer not connected
or read value outside of the permit-
ted range
4.4.2
Temporary Errors
Message
Error No.
Description
Err
29
Flue temperature too high
Err
36
Triggering (open circuit) of one or
both pressure switches connected
to the INAIL input.
Only for 45 kW / 55 kW / 70 kW mod-
els based on what is required by
current legislation.
Err
38
Flow meter disconnected or flow
rate lower than minimum flow rate
Err
41
Primary circuit pressure insufficient
(temporary)
Err
60
Domestic hot water probe in short
circuit or disconnected.
Err
70
Delivery sensor short circuit or
disconnection. Delivery sensor
fault/delivery sensor temperature
overload
Err
80
Return sensor fault/return sensor
temperature overload
Err
90
Flue sensor faulty
Err
99
Too many resets from remote con-
trol. NO MORE RESETS
Err
100
Communication lost in zone 1 (tem-
porary)
Err
101
Zone 1 limit thermostat triggering
(temporary)
Err
102
Zone 1 delivery probe (temporary)
Err
104
Communication lost in zone 2 (tem-
porary)
Err
105
Zone 2 limit thermostat triggering
(temporary)
Err
106
Zone 2 delivery probe (temporary)
Err
108
Communication lost in zone 3 (tem-
porary)
Err
109
Zone 3 limit thermostat triggering
(temporary)
Err
110
Zone 3 delivery probe (temporary)
4.4.3
Warnings
Message
Error No.
Description
Atte
43
Venting cycle in progress (tem-
porary)
Air
44
Primary circuit pressure too high
(temporary)
Atte
46
Pressure decreasing alarm (<0.8)
(temporary)