31
20040170
GB
Start-up, calibration and operation of the burner
6.4
Adjustments prior to ignition (gas)
In addition, the following adjustments must also be made:
Slowly open the manual valves situated upstream from the
gas train.
Adjust the minimum gas pressure switch (Fig. 35) to the start
of the scale.
Adjust the maximum gas pressure switch (Fig. 34) to the end
of the scale.
Adjust the air pressure switch (Fig. 33) to the start of the scale.
Purge the air from the gas line.
We recommend using a plastic tube routed outside the build-
ing and to purge air until gas is smelt.
Fit a U-type pressure gauge or a differential pressure gauge
(Fig. 32), with socket (+) on the gas pressure of the pipe
coupling and (-) in the combustion chamber.
The manometer readings are used to calculate MAX burner
output.
Connect two lamps or testers to the two gas line solenoids to
check the exact moment in which voltage is supplied.
This operation is unnecessary if each of the two solenoid
valves is equipped with a pilot light that signals voltage pass-
ing through.
6.5
Burner start-up (gas)
Close the remote controls and position the selector 1)(Fig. 31) to
“
AUTO
”.
Position the selector 2) to “
GAS
” to select gas as fuel.
Make sure that the lights or testers connected to the solenoids, or
the pilot lights on the solenoids themselves, indicate that no volt-
age is present. If voltage is present, stop the burner immediately
and check the electrical connections.
When the limit thermostat (TL) closes, the “
CALL FOR HEAT
” 3)
signal must come on. The burner will subsequently begin its start-
ing cycle.
6.6
Burner ignition
The burner should light after having performed the above steps.
If the motor starts up, but the flame does not appear and the con-
trol box goes into lockout, reset it and wait for a new ignition at-
tempt.
If ignition is still not achieved, it may be that gas is not reaching
the combustion head within the safety time period of 3 seconds.
In this case increase gas ignition delivery.
The arrival of gas at the sleeve is indicated by the U-type manom-
eter (Fig. 32).
If further burner lockouts occur, refer to the “Release procedure”
given in the equipment manual supplied.
Once the burner has fired, now proceed with global calibration
operations.
6.7
Change of fuel
There are three options of change of fuel:
1
with the AZL device 4)(Fig. 31);
2
with selector 2);
3
with a remote selector connected to the main terminal board.
The AZL device sets the priority fuel; the display shows the se-
lected fuel.
Positioning the selector 2)(Fig. 31) to “EXT” activates the remote
selection of the fuel. In this position, if there is no remote selector,
the display shows the priority fuel.
CAUTION
Before starting up the burner, it is good practice to
adjust the gas train so that ignition takes place in
conditions of maximum safety, i.e. with gas deliv-
ery at the minimum.
Fig. 32
D11318
Содержание 1311 T2
Страница 2: ...Translation of the original instructions...
Страница 46: ...20040170 44 GB Appendix Electrical panel layout 0 0 0 0 0 0 0 0...
Страница 47: ...45 20040170 GB Appendix Electrical panel layout...
Страница 49: ...47 20040170 GB Appendix Electrical panel layout...
Страница 50: ...20040170 48 GB Appendix Electrical panel layout 0 0 1 0 1 2 0 3 0 1 0 1 1 0 0 0 0 0 40 4 4 0 0 1 2 0 1...
Страница 51: ...49 20040170 GB Appendix Electrical panel layout 0...
Страница 52: ...20040170 50 GB Appendix Electrical panel layout 0 1 1 1 2 1 3 1 1 1 1 1 1 1 41 4 4 1 1 2 1...
Страница 53: ...51 20040170 GB Appendix Electrical panel layout 0 0 1 2 0 0 3 3 3 0 1 4...
Страница 56: ...20040170 54 GB Appendix Electrical panel layout 0 1 1 1 1 1 2 2 2 0 2 2 2 2 2 2 2 2 2 2 2 0 2 3...
Страница 57: ...55 20040170 GB Appendix Electrical panel layout 01 233 23 4 4 4 5 4 6 4 4 4 4 4 4 4 4 4 4 5 4...
Страница 59: ......