- 13 -
P
OWER CONNECTION INFORMATION
INPUT AC Line Connection 3PH + N + PE
Table 17
UPS
size
[kVA]
Max current [A]
Terminal L1, L2, L3, N
PE
Suggested wire L1, L2, L3, N, PE
(
*
)
PH + N
connection
3PH + N
connection
Max cross
section
[sqmm]
Max
Tightening
torque
[Nm]
Bolt
size
Cross
sectional area
L2, L3
[N x sqmm]
Cross
sectional area
L1, N, PE
(
**
)
[N x sqmm]
Type
10
66
22
16
3
M6
1 x 2.5
1 x 10
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
15
102
34
35
5
M6
1 x 4
1 x 16
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
20
120
40
35
5
M6
1 x 6
1 x 25
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
BYPASS AC Line Connection PH + N + PE (Dual Input)
Table 18
UPS
size
[kVA]
Max
Continuous
current
[A]
Terminal L1B, N
PE
Suggested wire L1B, N, PE
(
*
)
Maximum cross
section
[sqmm]
Tightening
torque
[Nm]
Bolt
size
Cross sectional
area
L1B, N, PE
(
**
)
[N x sqmm]
Type
10
48
16
3
M6
1 x 10
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
15
24
35
5
M6
1 x 16
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
20
32
35
5
M6
1 x 25
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
OUTPUT AC Line Connection PH + N + PE
Table 19
UPS
size
[kVA]
Nominal
current In
[A]
Terminal L, N
PE
Suggested wire L, N, PE
(
*
)
Maximum cross section
[sqmm]
Tightening torque
[Nm]
Bolt size
Cross sectional area
L, N, PE
(
**
)
[N x sqmm]
Type
10
43.5
16
3
M6
1 x 10
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
15
65.2
35
5
M6
1 x 16
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
20
87
35
5
M6
1 x 25
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
Input Battery DC Line Connection BATT+, BATT-, BATT N, PE (Nominal v240V, -240V)
Table 20
UPS
size
[kVA]
Rated Current [A]
Terminal
BATT +, BATT -, BATT N
PE
Suggested wire BATT +, BATT -, BATT N, PE
(
*
)
@nominal
battery
voltage
@end of
discharge
voltage
Maximum
cross section
[sqmm]
Tightening
torque
[Nm]
Bolt
size
Cross sectional area
+, -, N, PE
(
**
)
[N x sqmm]
Type
10
22
27
10
1.9
M6
1 x 6
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
15
33
42
16
3
M6
1 x 10
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
20
44
55
16
3
M6
1 x 16
FG16R16-0,6/1 kV (90°C)
or FG7R (90°C)
(*)
The suggested cross section refers to 90°C rated cables with an ambient temperature of 30°C. If different cables are used, or
installed at a higher ambient temperature, the cable size needs to be reviewed.
The cross sections indicated in the table refer to a maximum length of 10 metres
(**)
We recommend using at least two PE connection cables. If only one cable is used, it must have a minimum section of 10 mm².
Содержание Sentryum S3M
Страница 1: ......
Страница 2: ......
Страница 18: ... COMPACT series 16 COMPACT POSITIONING INFORMATION ...
Страница 24: ... ACTIVE series 22 ACTIVE POSITIONING INFORMATION ...
Страница 25: ... ACTIVE series 23 POWER CONNECTION INSTALLATION REMOVE THE FRONT TERMINAL COVER ...
Страница 31: ... XTEND series 29 XTEND POSITIONING INFORMATION ...
Страница 32: ... XTEND series 30 POWER CONNECTION INSTALLATION REMOVE THE FRONT TERMINAL COVER ...
Страница 41: ... 39 REMOVING DOOR ACTIVE MODEL XTEND MODEL ...
Страница 42: ... 40 ...
Страница 43: ......
Страница 44: ...0MNS3TK10RUENIA ...