- 11 -
SENTRYUM SINGLE PHASE - S3M
E
XTERNAL PROTECTIVE DEVICES
RCD
BREAKER
(R
ESIDUAL
C
URRENT
D
EVICE
)
If an input isolation transformer is not present, the neutral from the mains power supply is connected to the UPS output neutral. As a
result, there will be no change to the neutral arrangements of the installation:
THE UPS INPUT NEUTRAL IS CONNECTED TO THE UPS OUTPUT NEUTRAL
THE DISTRIBUTION SYSTEM THAT POWERS THE UPS IS NOT MODIFIED BY THE UPS
The neutral condition is only modified if an isolation transformer is present or when the UPS works with the neutral
isolated upstream.
Make sure that the equipment is properly connected to the input neutral, otherwise serious damage can occur
to the UPS.
During normal operation, when the mains supply is present, an RCD breaker at the input of the UPS will activate if a fault occurs at
the output side, since the output circuit is not isolated from the input.
In any case, other RCD breakers may still be installed at the output, preferably in coordination with those present at the input.
The earth leakage current may exceed 3.5mA, so the RCD breaker located upstream must have the following characteristics:
Differential current adjusted to the sum of UPS + Load; we recommend keeping a suitable margin to prevent nuisance tripping
(100mA min. - 300mA recommended)
Type
B
Delay of at least 0.1s
NOTE for DUAL INPUT connection:
1. A single RCD breaker must be installed upstream at the point where the sources divide to supply the standard input and the
bypass input of the UPS (refer to
22
).
2. If the standard input and the bypass input are supplied from two separated sources, then it is required to use a dedicated
RCD device for each source.
B
ACKFEED PROTECTION
The UPS has an internal protection against backfeed. This protection acts by means of a sensing circuit which turns the inverter off if
a fault within the static switch is detected. During this condition, to avoid interrupting the supply to the connected load, the UPS
switches to the bypass line.
If this fault occurs during battery operation, the inverter is stopped.
A volt free contact can be configured to drive a disconnecting device to be installed upstream of the bypass input to the UPS, in this
case when a backfeed fault occurs, the system opens the external disconnecting device, hence avoiding the requirement to stop the
inverter (refer to the user manual to configure this option).
The label supplied with the UPS must be affixed to all disconnectors installed within the electrical system upstream of
the UPS.
T
HERMAL
-
MAGNETIC CIRCUIT BREAKERS
As previously explained, the UPS has protection devices for output faults as well as for internal faults.
In order to configure the power source, a thermal-magnetic switch must be installed upstream of the UPS.
Please follow the indications in the table below:
Automatic external protective devices
Table 12
UPS Model
Mains input
Bypass Input (P+N)
Single-phase input (P+N)
Three-phase input (3P+N)
10
80A (trip characteristic curve “C”)
63A (trip characteristic curve “C”)
N.D.
15
100A (trip characteristic curve “C”)
100A (trip characteristic curve “C”)
N.D.
20
125A (trip characteristic curve “C”)
100A (trip characteristic curve “C”)
N.D.
10 - UPS with Dual Input
80A (trip characteristic curve “C”)
40A (trip characteristic curve “C”)
63A (trip characteristic curve “C”)
15 – UPS with Dual Input
100A (trip characteristic curve “C”)
50A (trip characteristic curve “D”)
100A (trip characteristic curve “C”)
20 - UPS with Dual Input
125A (trip characteristic curve “C”)
50A (trip characteristic curve “D”)
100A (trip characteristic curve “C”)
If the protective device upstream of the UPS interrupts the neutral wire, it must also interrupt all of the phase wires at
the same time (4-pole breaker).
Please select the thermal-magnetic circuit breakers in accordance with the “SHORT CIRCUIT WITHSTANDING” below.
Содержание Sentryum S3M
Страница 1: ......
Страница 2: ......
Страница 18: ... COMPACT series 16 COMPACT POSITIONING INFORMATION ...
Страница 24: ... ACTIVE series 22 ACTIVE POSITIONING INFORMATION ...
Страница 25: ... ACTIVE series 23 POWER CONNECTION INSTALLATION REMOVE THE FRONT TERMINAL COVER ...
Страница 31: ... XTEND series 29 XTEND POSITIONING INFORMATION ...
Страница 32: ... XTEND series 30 POWER CONNECTION INSTALLATION REMOVE THE FRONT TERMINAL COVER ...
Страница 41: ... 39 REMOVING DOOR ACTIVE MODEL XTEND MODEL ...
Страница 42: ... 40 ...
Страница 43: ......
Страница 44: ...0MNS3TK10RUENIA ...