7.
General characteristics
UPS models
160kVA
200kVA
250kVA
MECHANICAL DATA
Width (inches [mm])
39.4 [1000]
Width (inches [mm]) TCE version *
55 [1400]
Depth / height (inches [mm])
33.46 [850] / 74.80 [1900]
Ventilation
Forced
Noise at 1m from front (0÷100% load)
(dBA)
68
Applicable Standards
UL Standard 1778 5
th
edition
UL 60950-1
National Electrical Code (NFPA-70)
CUL to CSA C22.2
FCC Part 15 Subpart J Class A
IEC 62040-3
*Version including Top Cable Entry + Manual Bypass
UPS models
160kVA
200kVA
250kVA
INPUT RECTIFIER
Rated voltage
480Vac 3-phase
Rated voltage tolerance without contrib.
of battery @100% load
-10%, +15%
Voltage tolerance in battery mode or
load depending
-40%, + 15%
Input frequency tolerance
from 45 to 65Hz
Rated current absorbed (480 V)
[A]
188
235
294
Rated power absorbed (480 V)-(kVA)
156
196
244
Maximum current absorbed at full load
and with battery recharging
[A]
212
265
331
Power factor at rated voltage (480 V)
and battery charge from 25% to 100%
of the load
>0.99
Current Harmonic Distortion (THDi)
(with mains distortion <1%)
% load
rated load at 100%
75%
25÷50%
≤ 3
≤ 5
≤ 8
Progressive start of rectifier (Power
Walk-in)
from 0 to 125 seconds (configurable)
Delay of progressive start of rectifier
(Power Walk-in delay timer))
from 0 to 125 seconds (configurable)