![Riello UPS Master-HP 160 Скачать руководство пользователя страница 62](http://html.mh-extra.com/html/riello-ups/master-hp-160/master-hp-160_user-manual_1460283062.webp)
page 62 / 85 0MLMHTM16RUENUB
1.1.26 Measurements menus (key 2)
The measurements with two line displayed, are selected from the basic menu by pressing key
2
Basic menu
1.1.27 Times Measurement.
OUT=277,277,277Vln
Measurement of the three output phase voltages of
the UPS, with the concatenated value in brackets.
100,100,100%A
Measurement of the three output currents. The
output currents are expressed as a percentage
of the rated value.
100,100,100%W
Measurement of the active output power. The power
is expressed as a percentage of the rated power.
60.1Hz
Output frequency.
147,147,147%Ap
Measurement of the three peak currents as a
percentage relating to the three output phases during
operation from inverter. During operation from
bypass, the message OUT changes to BY.
IN=100,100,100%V, 60.2Hz
Measurement of the three voltages, neutral phase and input
frequency. The voltage is indicated as a percentage of the rated
voltage; for example 100% is equivalent to 277V.
101,101,101%A
Measurement of the three input currents. The input currents are
expressed as a percentage of the rated value.
BY=277,277,277Vln(480V)
Measurement of the three input phase voltages of the bypass line,
with the concatenated voltage (the average of the three values) in
brackets.
60.1Hz
Frequency of the bypass line.
BATT=xxxV
battery voltage value;
+0.0A
battery current, positive with
Battery discharging, negative
with battery charging;
i=277,277,277Vln
inverter output voltage;
yyyVdc
input
inverter DC voltage
Ts=28, Tr=50, Ti=49, Tb=25;
Temperature of the system, and of the rectifier
and inverter modules, Tb is present only if the
external temperature the sensor is installed;
OUT=10000h
hours of normal operation
BY=10000h
hours of operation from bypass
BATT=10000sec
time spent in operation from battery
nBATT = 1000
number of times the battery has discharged
n0%Ah = 100
number of times the battery has discharged
fully
2007-01-01
data stored on first start-up of the UPS.
These are HISTORY data, and remain stored even when the
device is switched off and may not be reset.
OUT= 277,277,277Vln(480V);100,100,100%A
100,100,100%W 60.1Hz;147,147,147%Ap
IN=100,100,100%V; 101,101,101%A; 60.1Hz
BY=277,277,277Vln (480V);60.1Hz;
BAT=xxxV; +0.0A; i=277,277,277Vln;yyyVdc
Ts=28,Tr=50,Ti=49,Tb=25;
OUT= 10000h; BY= 10000h; BATT= 10000sec
nBATT= 1000; n0%Ah= 100; 2007-01-01