6
TECHNICAL DATA
(1) Reference conditions: Ambient temperature 20°C - Barometric pressure 1000 mbar - Altitude 100 m s.l.m.
(2) Pressure at test point 8) (A) p.8, with zero pressure in the combustion chamber and maximum burner output.
(2) Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and at maximum rated output.
ACCESSORIES
(optional):
•
OUTPUT POWER REGULATOR KIT:
Under modulating operation, the burner automatically adapts to one of an infinite number of firing rates
between the low and high flame output position, thus ensuring stable operating conditions in terms of temperature or pressure. Two components
should be ordered: • Power regulator to install on the burner; • probe to install on the boiler.
•
GAS TRAIN ACCORDING TO REGULATION EN 676 (with valve, pressure governor and filter):
see page 18.
MODEL
RS 45/M BLU
TYPE
827 T2
OUTPUT
(1)
MAX.
kW
190 - 550
164 - 474
Mcal/h
MIN.
kW
90
78
Mcal/h
FUEL
NATURAL GAS: G20 - G21 - G22 - G23 - G25
G20
G25
- Net calorific value
kWh/Nm
3
Mcal/Nm
3
10
8,6
8,6
7,4
- Absolute density
kg/Nm
3
0,71
0,78
- Max delivery
Nm
3
/h
55
64
- Pressure at maximunm delivery
(2)
mbar
13,5
17,5
OPERATION
• Intermittent (min. 1 stop in 24 hours)
• Progressive two-stage or modulating by kit (see ACCESSOI-
RES).
STANDARD APPLICATIONS
Boilers: water, steam, diathermic oil
AMBIENT TEMPERATURE
°C
0 - 40
COMBUSTION AIR TEMPERATURE
°C max
60
ELECTRICAL SUPPLY
V
~ 50 Hz 230 V (+/- 10%)
ELECTRIC MOTOR
W
V
A
420
220 - 240
2,9
MOTOR CAPACITOR
µF / V
12,5/450
IGNITION TRANSFORMER
V1 - V2
I1 - I2
220/240 V - 1x15 kV
45 vA - 25 mA
ELECTRICAL POWER CONSUMPTION
W max
600
ELECTRICAL PROTECTION
IP 44
ELECTROMAGNETIC COMPATIBILITY
90/396 - 89/336 - 73/23 - 92/42
NOISE LEVELS
(3)
dBA
70
APPROVAL
CE
APPROVAL
BUWAL Nr
COUNTRY
CATEGORY
SE - FI - AT - GR - DK -ES - GB - IT - IE - PT - IS - CH - NO
DE
NL
FR
BE
LU
I
2H
I
2ELL
I
2L
I
2Er
I
2E(R)B
I
2E
PARAMETER TO BE CHECKED
PROBE
POWER REGULATOR
Range
Type
Code
Type
Code
Temperature
- 100...+ 500°C
PT 100
3010110
RWF40
3010212
Pressure
0...2,5 bar
0...16 bar
Output probe
4...20 mA
3010213
3010214
Important:
The installer is responsible for the addition of any safety device not foreseen in this manual.