15-
Parameter
Description
Operation setting for
unit type:
GEKN
GEKT
P30
Alarm mode (0= for alarm exit active)
(6= for remote control)
6 2)
6 2)
P31
Delay time for alarm
90 min.
90 min.
P32
Upper alarm temperature
P03 + 8 K
P03 + 10 K
P33
Lower alarm temperature
- 6°C
- 30°C
P34
Command input (0 = deactivated)
(1 = door contact)
0 2)
0 2)
P35
Delay time for command input
30 min. 2) 30 min. 2)
P36
Upper value voltage output
0
0
P37
Lower value voltage output
0
0
P38
Mode voltage output (0 = off)
0
0
P39
State of the temperature listings
(0 = Off, 2 no listings)
0 0
P40
Intervals for listings
15 min.
15 min.
P41 date
entry,
year
--
--
P42 date
entry,
month
--
--
P43 date
entry,
day
--
--
P44 time
entry,
hour
--
--
P45 time
entry,
minute
--
--
P46 time
entry,
second
--
--
P47
Baud rate 5 = 19200 Baud)
5
5
P48
Unit address in the network
78
78
P49 Manual
defrost
--
--
P50 Code
input
88 88
Attention: Never change parameters P47 or P48 of the remote control. This would
interrupt the communication between the remote control and the cooling cell controller.
If these parameters are changed for any reason, then the communication to the cooling cell
controller can only be restored via the setting mode of the remote control. The baud rate and the
unit address must be set to have the same values as P47 and P48.
8) Technical data
Compact, ready-to-use refrigeration units for all cold storage cells with refrigeration temperatures
from –25°C to –5°C, or -5°C to 12 ° C (extra-low temperature and standard cooling).
(Maximum permissible temperature up to 16°C)
Delivery contents and delivery status:
Stable, torsionally stiff housing, colour: white, powder coated, suitable to be mounted on a cell
element with a wall thickness of 70 – 120mm, with a fan guards for the evaporation fan according
to DIN 31001.
Complete refrigeration equipment consisting of:
- sealed compressor with a winding protection switch
- ventilated
condenser
- ventilated
evaporator
- thermostatic expansion valve
- collector
dryer
- automatic, electronic defrosting with a timer and demand-optimized defrost function